Maintenance; Maintenance And Inspections Schedule - Harsco Industrial SC-2000 Installation & Owner's Manual

Gas fired boiler
Hide thumbs Also See for SC-2000:
Table of Contents

Advertisement

 
Lockout/tagout procedure must be
employed when servicing this unit.
Failure to do so could result in
electrocution, injury, or death.
Label all wires prior to
disconnection when servicing
controls. Wiring errors can cause
improper and dangerous operation.
Use care when reassembling main
gas line and ensure all connections
are tight. Use a leak detector to
check for leaks before and after
servicing any component of the
gas piping. Failure to do so could
result in injury or death.
Use care when servicing boiler to
prevent the accumulation of gas in
or around the combustion
chamber. Pockets of accumulated
gas are subject to combustion
and/or explosion which could result
in injury or death.
Determine the cause of any lockout
or errors before resetting the boiler.
If able to determine cause of
lockout, then appropriate corrective
action should be taken. If unable
to determine cause of the problem,
call a qualified service technician.
Verify proper operation after
servicing.
 
Check daily to be sure that the
boiler area is free and clear of any
combustible materials, including
flammable vapors and liquids.
 
Harsco Industrial, Patterson-Kelley Technical Service 1.877.728.5351

5 Maintenance

 

5.1 Maintenance and Inspections Schedule

This schedule applies when the boiler is in use. Verify proper
operation after servicing. NOTE: The blower motor is permanently
lubricated and does not require periodic lubrication.
5.1.1 Daily
Observe operating temperature and general conditions.
 
sure that the flow of combustion and ventilating air to the boiler is
not obstructed. Determine the cause of any service codes or
lockouts on the display panel. Observe any unusual noises or
operating conditions and make the necessary corrections. Notify
responsible individuals for required corrective action or repair.
5.1.2 Weekly
Observe the conditions of the main flame. A normal high fire flame
 
is mostly orange with a blue halo, while at low fire the burner will
glow yellowish-orange.
Correct air adjustment is essential to the efficient operation of this
boiler. Ensure that the flow of combustion and ventilation air is not
obstructed.
If an adjustment in the combustion appears necessary, the flue
gas composition should be checked with a carbon dioxide (
oxygen (
3.11.2
necessary, call a qualified and knowledgeable installer or service
 
agency that has been trained on the Harsco Industrial, Patterson-
Kelley boilers.
5.1.3 Monthly
1. Press the "Info" button on the NURO touch screen to load
the Information Screen and scroll down to view the flame signal
measured in Volts. Typical flame signals should read between
20-50V. If the flame signal is below 20V, the ignition electrode
may need to be replaced.
2. Test the low water level cut-off.
 
3. Test the manual reset high-temp limit.
4. Test low gas pressure switch.
5. Test operating temperature controls by reducing or
increasing temperature setting as necessary to check burner
operation.
6. Check the condensate drain system. Clean and flush as
necessary.
Installation and service must be performed by a qualified and
knowledgeable installer or service agency that has been trained
on the Harsco Industrial, Patterson-Kelley boilers.
 
) analyzer and compared to the values stated in
O
2
of
Section
3.11.2. If an adjustment to the combustion is
38
Gas Fired Boiler
Refer to Section
3.9.2.
Refer to Section
Refer to Section
3.9.4.
Make
) or
CO
2
Table
3.9.3.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sc-3000Sc-4000

Table of Contents