3.3.1.3 Canadian Considerations

Air inlet requirements for the Canada States are established by CAN/CSA B149.1.
1.
The free area of a combustion air supply opening is calculated by deducting the
blockage area of any fixed louvers, grilles or screens from the total area of the
opening.
2. Screens shall be not smaller than ¼ inch.
3. Motorized louvers shall be interlocked with the appliance so that they are proven
open prior to main burner ignition and operation.
A. A. Ventilation of the space occupied by fuel burning appliance(s) or equipment shall be supplied by a
ventilation opening at the highest practicable point communicating with the outdoors. The total cross
sectional area of the ventilation opening must be either 10% of the net free area required for
combustion air or 10 sq. in. (6500 mm
B.
Use the following opening calculation for
When combustion air is supplied for a forced draft burner by natural airflow from the outdoors and
there is no draft regulator or draft hood in the same space, there shall be a permanent opening with a
cross sectional area not less than 1 sq. in/30,000 Btu/Hr (70 mm
burner(s). This opening must not interfere with the ventilation air opening defined in paragraph A.
C. Use the following opening calculation for
appliances:
When combustion air is supplied for natural or fan-assisted burners by natural airflow from the
outdoors, there shall be a permanent opening with a cross sectional area not less than 1 sq. in/7000
Btu/Hr (321 mm
in excess
of
1,000,000 Btu/Hr. This opening must be either located at or ducted to a point not more
than 18 in. (450 mm) or less than 6 in. (150 mm) above floor level. This opening is in addition to the
ventilation air opening defined in paragraph A.
D. When combustion air is supplied by natural airflow into a space containing both types of appliance
described in paragraphs B and C, the cross sectional area of the opening shall not be less than the
sum of the cross sectional areas for all appliances in the space as calculated by the applicable
method. This opening is in addition to the ventilation air opening defined in paragraph A.
E. When a duct is used to meet the requirement for combustion air supply, as described in paragraphs A
through D, above, the opening of the duct shall be located so there is no possibility of cold air
affecting steam or water piping, electrical equipment or mechanical equipment.
US Minimum Area of Ventilation Openings per Boiler (Sq In)
INDOOR AIR SUPPLY
SAME
FLOOR
1500
2000
3000
4000
2
/kW) up to and including 1,000,000 Btu/Hr plus 1 sq. in./14,000 Btu/Hr (155 mm
AIR SOURCE
DIFF
ONE
FLOORS
OPENING
3000
500
4000
667
6000
1000
8000
1334
NOTE
2
), whichever is greater.
TM
P-K SONIC
boilers:
boilers or other natural draft or fan-assist
P-K THERMIFIC®
TM
P-K SONIC
Gas Fired Boiler
T T T T echnical Service 1.877.728.5351
echnical Service 1.877.728.5351
echnical Service 1.877.728.5351
echnical Service 1.877.728.5351
OUTDOOR AIR SUPPLY
TWO OPENINGS
VERT
DIRECT
DUCT
375
375
500
500
750
750
1000
1000
2
/kW) of the total rated input to the
HORIZ
DUCT
750
1000
1500
2000
2
/kW)