Clearance From Combustible Materials - J. A. Roby SUROIT / RGV-25 Installation And Operation Manual

Direct-vented gas fireplaces
Hide thumbs Also See for SUROIT / RGV-25:
Table of Contents

Advertisement

3.1.2

CLEARANCE FROM COMBUSTIBLE MATERIALS

MINIMUM CLEARANCE WITH COMBUSTIBLE
Glass doors to opposite
walls - All models
Vent to walls - All models
Top of fireplace to ceiling -
All models
Back of fireplace to
adjacent material - Models:
LOO, MISTRAL, AUSTER
MOUSSON, and SIROCCO
WARNING:
A combustible surface located above the visible faces of the fireplace must not overhand these faces by
more than 3/4" (2 cm). A surface exceeding this limit is considered a mantle and must comply with the
requirements on shelves described in section 3.1.5 of this manual.
To make installation easier, put the appliance in place and install the vent system before framing the fireplace.
Remember to install the required clearance post on top.
WARNING:
Before framing your fireplace, check dimensions, framing methods and finished wall facing details.
Determine the total thickness of the finishing material – drywall, ceramic, tile, slate, etc. Make sure the
finished surface will be flush with the front or side of the unit.
.
If you install your fireplace on an outside wall or in an alcove, use a firewall and drywall in compliance with local
building codes.
MATERIALS
42" (107 cm)
3" (8 cm) for the first 8 ft. of
vent (unless protected by a
firewall) and 1" (25.4 mm) for
the rest of the vent.
21¼" (54 cm )
0" (0 mm)
30