Suroit / Rgv -25 ( See Through ) With Top Exit; Clearance From Combustible Materials - J. A. Roby loo RGR-25 Installation And Operation Manual

Direct-vented
Hide thumbs Also See for loo RGR-25:
Table of Contents

Advertisement

3.1.2.17. S
/
UROIT
RGV

3.1.3. CLEARANCE FROM COMBUSTIBLE MATERIALS

Glass doors to opposite walls
- All models
Vent to walls - All models
Top of fireplace to ceiling
- All models
Back of fireplace to adjacent material
- Models: LOO, MISTRAL, AUSTER
MOUSSON, and SIROCCO
A combustible surface located above the visible faces of the fireplace must not overhand these
faces by more than 3/4" (2 cm). A surface exceeding this limit is considered a mantle and must
comply with the requirements on shelves described in section 3.1.5 of this manual.
32
-25 (
)
SEE THROUGH
WITH TOP EXIT
MINIMUM CLEARANCE WITH COMBUSTIBLE MATERIALS
42" (107 cm)
3" (8 cm) for the first 8 ft. of vent
(unless protected by a firewall) and 1"
(25.4 mm) for the rest of the vent.
21¼" (54 cm)
0" (0 mm)
WARNING