a. Installation of Air Panel for Wireless Control
In case of simultaneous operation of plural (up to 16)
units by the wireless remote control switch, apply the air
panel for wireless control only to the unit to be
operated, and apply the standard panels (for wired
control) to other units. In case of applying plural air
panels for wireless control, up to 2 air panels for
wireless control can be used.
Wireless
Standard
Panel
Panel
Should be Standard Panel
Wireless
Controller
In case of applying two (2) air panels for wireless control,
the setting of main and sub receiver part is required. Refer
to the item 4.4.5 "Optional Function Setting" for the dip
switch setting procedures.
b. Perform wiring between indoor units as shown in the
figure below.
* The total length of the wire shall be 200m or shorter.
(for 0.75mm~ wire 500m or shorter)
* Use the following three cable wire in the system parts.
Model
PRC-10E
Length
10m
CN12(Yellow)
2-Cores(Red & Black) or 3-cores
"Multi"
PCB of Main Unit
CN13(Blue)
"Remote
Control"
CN13(Blue)
"Remote Control"
CN12(Yellow)
"Multi"
Receiver
Rotary Switch (RSW)
Setting When Shipment
c. Connected unit control wires should not be installed
parallel to 220-415V power cables. Fix them by utilizing
bands. It is recommended that cables be installed at
least 30cm away from power cables or be put into
grounded metal pipes.
Standard Panel or
Standard
Wireless Panel
Panel
PRC-15E
PRC-20E
15m
20m
2-Cores(Red & Black) or 3-cores
2-Cores(Red & Black) or 3-cores
PCB of Branch Unit (No.1)
PCB of Branch Unit (No.2)
CN13(Blue)
CN12(Yellow)
"Remote
Use 3-core cable
"Multi"
Control"
of 0.3-0.75mm²
(SEE TABLE)
OPTIONAL FUNCTION
d. Set the Rotary Switches (RSW) on the printed circuit
boards of respective units as shown in the next table.
Unit nº 0
Unit nº 1
Unit nº 4
Unit nº 5
Unit nº 8
Unit nº 9
Unit nº 12
Unit nº 13
&
CAUTION:
If the setting of the Rotary Switches (RSW) is not
performed correctly, the operation LED (Red) on
the panel flickers and the unit can not be operated
due to the abnormal setting of the indoor unit
number.
e. Identify the indoor units by attaching the nameplates of
unit number (field-supplied) to the indoor units when
setting the rotary switches (RSW) for each indoor unit.
Nameplates of
Receiver Part
Unit Number
4
21
Setting position
Set by inserting a
screwdriver into the
groove.
Unit nº 2
Unit nº 3
Unit nº 6
Unit nº 7
Unit nº 10
Unit nº 11
Unit nº 14
Unit nº 15