WARNING: TURN OFF all power source switches
NOTE:
Do not remove the screw (B).
If removed, the drain-up mechanism will drop
2.3.9

REMOVING DRAIN PAN

1. Remove the optional air panel according to the item, 2.3.4,
"Removing Optional Air Panel".
2. Disconnect the connectors between indoor unit and
outdoor unit, and in the electrical box after opening the
electrical box cover according to the item, 2.3.3, "Removing
Electrical Box Cover".
3. Remove the bell-mouth according to No.3 of item, 2.3.5,
"Removing Turbo Fan and Fan Motor".
4. Remove drain water.
5. Remove the drain pan after removing four (4) screws fixing
the drain pan onto the indoor unit.
SERVICING
Drain-Up
Mechanism
Hose Band
Drain Hose
Drain Pan
2
19
Fixing Plate for
Drain-Up
Mechanism