Dip Switch Configuration - VESDA VLQ-100 Product Manual

Vlq series
Table of Contents

Advertisement

VESDA VLQ Product Guide
5.3

DIP Switch Configuration

The VESDA VLQ provides a range of configuration options using an on-board DIP Switch bank.
Switch Position
1,2,3
Set Fire Alarm Smoke
Threshold (Pre-alarm set
to 50% of Fire Alarm
automatically)
4
Set Fire Alarm Delays
5
Set Flow Delays
6
Set Fire Alarm latching
7
Set Fault latching
8
Set Flow Fault Limits
30
Figure 5-1: DIP Switch Location
Table 5-1: DIP Switch Configuration
Purpose
Configuration
SW1 SW2 SW3
OFF OFF OFF
ON
OFF
ON
OFF OFF
ON
OFF
ON
Options
0.15%/m (0.046%/ft)
OFF OFF 0.3%/m (0.091%/ft)
ON
OFF 0.6%/m (0.18%/ft)
ON
OFF 0.8%/m (0.28%/ft)
ON 1.0%/m (0.30%/ft)
OFF
ON 1.5%/m (0.46%/ft)
ON
ON 2.0%/m (0.61%/ft)
ON
ON 3.0%/m (0.91%/ft)
OFF
No Delay
ON
30s Delay
OFF
No Delay
ON
30s Delay
OFF
Fire Alarms not latched
ON
Fire Alarms latched
OFF
Faults not latched
ON
Faults latched
OFF
+/-20%
ON
+/-50%
VESDA by Xtralis
Default Switch
Settings
0.3%/m
(0.091%/ft)
OFF (No Delay)
OFF (No Delay)
ON (Latched)
ON (Latched)
ON (+/-50%)
www.xtralis.com