Configuration - VESDA VLQ-100 Product Manual

Vlq series
Table of Contents

Advertisement

VESDA VLQ Product Guide
Button / Function
Set Time
Get Event Log
Get Smoke
7.3

Configuration

Table 7-2 below details VLQ configuration items available in the Xtralis QSC software, under Device
Configuration.
Configuration Item
Configure via Xtralis QSC
Unit
Fire Alarm Threshold
Pre-Alarm Threshold
Alarm Delay
Alarm Latching
Fault Latching
Flow Fault Limit
Fault Delay
GPI Configuration
Buzzer
34
Table 7-1: Xtralis QSC Commands (continued...)
Action
Allows setting of the detector time, chose set to PC time for this version
Allows to log up to last 1000 events and stores in a CSV file (do not change
any timing on the right side up down button)
Allows logging of smoke at between 1 and 60 second intervals and stores in
a CSV file, this is useful to determine minimum and maximum thresholds
settings during the fire tests if required. It is recommended that the smoke
interval is set to 10 seconds or greater. This is a live smoke data capture so
Xtralis QSC must be running during this function.
Table 7-2: Configuration Items
Description
Allow configuration of the
detector from Xtralis QSC.
Set the units of smoke
Set the threshold of Fire alarm
Set the threshold of Pre-alarm
Configure delay of fire alarm
Allows to latch the fire relay
Allows to latch the fault relay
Set the limit of flow fault
Configure delay of fault
Configure the GPI action
Enable or disable buzzer
VESDA by Xtralis
Parameters / Range
Enable/Disable
Metric/Imperial
0.15%obs/m - 3%obs/m
(0.046%/ft - 0.915%/ft)
0.1%obs/m - 1.5%obs/m
(0.03%/ft - 0.457%/ft)
0, 30, 45 or 60 seconds
Enable/Disable
Enable/Disable
+/-20%, +/-50%
0, 30, 45 or 60 seconds
Reset
l
External Device (PSU)
l
Monitoring
Reset+Disable
l
Standby
l
Enable/Disable
www.xtralis.com