Baxi Solo 2 60 RS Installation And Servicing Instructions page 27

Wall mounted room sealed gas fired central heating boilers
Table of Contents

Advertisement

Commissioning The Appliance - Page 27
Turn on main electricity supply.
Light burner by turning thermostat knob to high setting (fully
clockwise).
Check pressure after 10 minutes. Adjust if necessary to the
relevant figures for the corresponding model shown in the
chart below.
To set the main burner pressure adjust the throttle as shown.
To increase the burner pressure, turn the adjustment screw
in either direction until the required pressure is obtained.
Set any timer control, room thermostats etc to the
customer's specific requirements.
Turn the boiler thermostat knob to the OFF position marked
O. Screw home the pressure test point screw. Turn the boiler
thermostat knob to the required setting. Make a final check
for gas soundness of all gas carrying joints on boiler.
Check operation of flame failure device. Turn gas control
knob clockwise in the-direction marked O. The control knob
cannot be depressed until ignition restart interlock device in
gas valve has disengaged. This takes 60 seconds
approximately. Pilot must not be relit for 3 minutes after shut
down.
The appliance is fitted with a pump overrun timer which
keeps the pump running (fully pumped systems only), when
any external control switches the appliance off. To check the
operation of this, turn programmer, time switch off, the pump
should continue to run for approximately 3 minutes and then
stop.
The boiler and system should be run and then flushed and
treated in accordance with BS7593: 1992 and the flushing
agent/inhibitor manufacturers instructions. When all the air
has been removed from the water circuit, the pump and
radiators should be balanced to achieve the design
temperature drop across the system. Recheck for water
leaks.
Carefully read and complete all sections of the "Benchmark"
Installation, Commissioning and Service Record Log Book
that are relevant to the appliance and installation. The details
of the Log Book will be required in the event of any warranty
work. The Log Book must be handed to the user for safe
keeping and each subsequent regular service visit recorded.
27