Baxi Solo 2 60 RS Installation And Servicing Instructions page 13

Wall mounted room sealed gas fired central heating boilers
Table of Contents

Advertisement

Site Requirements - Page 13
WARNING
If a terminal is less than 2 metres (78¾ in) above a balcony,
above ground or above a flat roof to which people have
access then a suitable terminal guard must be provided.
Terminal Position with Minimum Distance
A
Directly below an openable window or other opening,
e.g. an air brick.
B
Below gutters, soil pipes or drain pipes.
C
Below eaves.
D
Below balconies or car port roof
E
From vertical drain pipes and soil pipes.
F
From internal or external corners.
G
Above ground, roof or balcony level.
H
From a surface facing a terminal.
I
From a terminal facing a terminal.
J
Vertically from a terminal on the same wall.
K
Horizontally from a terminal on the same wall.
L
For an opening in a car port (e.g. door, window) into a
dwelling.
Flue Dimensions
Recommendations for flues are given in BS 5440:1.
The standard flue terminal supplied with the appliance is
suitable for use with wall thickness between 100mm (4in)
and 356mm (14in).
A flue terminal extension kit is available as an optional extra
for wall thickness between 356mm (14in) and 610mm (24in)
from the manufacturer. Quote appliance Model N° when
ordering.
13
mm
300
300
300
600
75
600
300
600
600
1500
300
1200