Baxi Solo 2 60 RS Installation And Servicing Instructions page 25

Wall mounted room sealed gas fired central heating boilers
Table of Contents

Advertisement

Installation - Page 25
FOR GRAVITY D.H.W. AND PUMPED C. H.
When the boiler is to be used on a system with gravity
D.H.W. ensure that the overheat thermostat has been
disconnected as shown.
The overheat thermostat is now by-passed and will allow the
appliance to perform satisfactorily on gravity circulation.
NOTE: Even though the overheat thermostat is not
operational, it must not be removed from the pocket in the
heat exchanger.
The recommended cable for connection to the appliance
2
terminal strip is 3-core 0.75mm
(24 x 0.2mm) P.V.C. IEC 53
code 227 (heat resistant).
WARNING: This appliance must be earthed.
Loosen securing screw sufficiently for the electrical cover to
be removed from the thermostat box.
Bare back input cable to dimensions shown.
Fit input cable to terminal block on left passing through the
grip provided.
The pump should be wired to the junction box or
programmer.
Replace electrical cover and securing screw.
A cable clip is supplied in the kit to secure the cable to the
bottom of the combustion
In the event of an electrical fault after installation of the
appliance, preliminary electrical system checks should be
carried out:- earth continuity, polarity and resistance to earth.
25