Installation distances to walls and ceiling
Stand the stove on a floor plate, ensuring that the stove is
no closer to the wall/ceiling than the minimum dis tances
indicated in the diagrams below. For stoves with a top flue
connection to a steel chimney, please refer to the assembly
and installation instructions for the relevant brand of chimney.
A =
height from floor to chimney connection
B =
height from floor to centre of hole for rear flue
C =
height from floor to air inlet
D =
height from floor to lower edge of door
510/550/550A
438
139
Ø150
30
97
Air inlet Ø67
400
300
200
100
Combustible wall
500
750
520T
470
139
Ø150
30
97
Air inlet Ø67
400
300
200
100
Combustible wall
468
750
Observe the minimum distances to combustible materials
prescribed by the manufac t urers of the chimney.
Allow at least 1.0 metre from the stove door to any combu-
stible part of the building structure or interior fittings.
If the stove will be installed on a turnabl e plate, the
A separate glass floor plate (accessory) increases
Combustible roof
the connection height to the chimney by 10mm.
Install the spacers supplied with the floor plate prior
496
Air inlet Ø67
800
Fire-retardant wall of
brick or concrete
565
Combustible roof
564
Air inlet Ø67
800
Fire-retardant wall of
brick or concrete
599
99
Important!
distances indicate d below will not be valid.
to connection.
Combustible wall
595
700
Fire-retardant wall of
brick or concrete
70*
320*
Combustible wall
629
700
Fire-retardant wall of
brick or concrete
38*
320*
GB
*See 570
*See 570