Model Number
Model Rating
DIMENSIONS: mm
Unit W x D x H
Shipping W x D x H
WEIGHT: kg
Unit
Shipping
INPUT AC PARAMETERS
Voltage Range
(typical)
100% - 90% loading
90% -70% loading
70% -30% loading
30% - 0% loading
Frequency
Input Connector
OUTPUT AC PARAMETERS
Output Sockets
Voltage
Frequency
Waveform
Main Mode
Overload
BATTERY PARAMETERS
Type
Qty x V x Rating
Battery Mfg/Part #
Back-up Time
Recharge Time
ENVIROMNMENTAL
Operating Temp
Storage Temp
Relative Humidity
Operating Elevation
Storage Elevation
Audible Noise
AGENCY
Safety
RFI/EMI
Surge Immunity
Transportation
SPECIFICATIONS
GXT2-2000RT230
2000VA / 1400W
87 x 547 x 430
268 x 692 x 585
24.7
28.7
230 VAC nominal; variable based on output load
176 VAC / 280 VAC
159 VAC / 280 VAC
139 VAC / 280 VAC
119 VAC / 280 VAC
200/208/220/230/240 (user configurable) VAC; ±3%
200% for 8 cycles; 130% for 10 seconds with transfer to bypass
Valve-regulated, nonspillable, flame retardant, lead acid
4 x 12V x 9.0 AH
5 Hours to 95% capacity after full discharge into 100% load
+32°F to +104°F (0°C to +40°C)
+5°F to +122°F (-15°C to +50°C)
Up to 3000m (10,000 ft.) at 40°C without derating
15,000 m (50,000 ft.) maximum
<55 dBA, at 1 metre from the rear
<50 dBA, at 1 metre from the front or sides
EN50091-1-1, CE compliance mark, for both Low Voltage and EMC
40 - 70 Hz; Auto Sensing
50 Hz or 60 Hz
Sinewave
Panasonic UP-VW1245P1
See Battery Runtime Charts
0% to 95%, non-condensing
Directives
EN 50091-2, Class
EN 61000 4-2, 4-3, 4-4, 4-5
ISTA Procedure 1A
34
GXT2-3000RT230
3000VA / 2100W
87 x 618 x 430
268 x 692 x 585
31.9
35.9
176 VAC / 280 VAC
159 VAC / 280 VAC
139 VAC / 280 VAC
119 VAC / 280 VAC
6 x 12V x 9.0 AH