Internal Battery replacement procedures:
1. Gently remove the front plastic bezel cover from the UPS.
2. Loosen and remove the four screws on the front battery door. Lay the
battery door aside for reassembly.
3. Gently pull battery wiring out and disconnect the 2 slotted battery con-
nectors.
4. Grasp the battery pack assembly, and pull it out of the front of the
UPS.
5. Unpack the new battery assembly taking care not to destroy the pack-
ing. Compare new and old battery assemblies to make sure they are
the same. If so, proceed with step 6; otherwise STOP and contact
your local dealer or Liebert Representative, or the Liebert Worldwide
Support Group.
6. Line up and slide in the new replacement battery pack.
7. Reconnect the 2 slotted battery connectors and gently push the bat-
tery wiring and battery pack assembly back into the UPS.
8. Reattach the front battery door with the four screws.
9. Reattach the front plastic bezel cover to the UPS.
NOTE: These are hot-swappable replacement batteries, caution should
be taken, as during this procedure the load is unprotected from distur-
bances and power outages.