(4 inches) clearance in front and rear of the UPS. Maintain an ambi-
ent temperature range of 0° to 40° C (32° to 104° F0° to 40° C).
NOTE: UPS operation in temperatures above 25° C (77° F) reduces
battery life.
7. Remove the front plastic bezel by grabbing and pulling forward evenly
on both sides. There are 2 front panel overlays, the tower configura-
tion ships on the unit. For Rack mounting, remove the front plastic
bezel cover and then the Tower display template overlay. Snap the
front plastic bezel cover back into place.
8. The UPS is now ready to be placed into the equipment rack.
9. Once the UPS is installed in the rack, the load may be connected.
Ensure the load equipment is turned off; plug all loads into the output
receptacles on the rear of the UPS.
10. Plug the UPS into a dedicated wall socket properly protected in
accordance with Local Codes and Regulations. The wall socket must
be grounded (earthed).
11. Turn ON the UPS by pressing the ON button; then turn ON the con-
nected load equipment. The UPS is now providing conditioned power
to your equipment.
10