Liebert UPSTATION GXT 2U User Manual page 18

Liebert power supply user manual
Hide thumbs Also See for UPSTATION GXT 2U:
Table of Contents

Advertisement

OFF/ Manual Bypass Button
This button controls output power to connected load(s) and has
dual functions: OFF and Manual Bypass.
CAUTION:
ferred to bypass power. Pressing this button a second time within 4 sec-
onds will result in loss of power to the output receptacles and connected
loads. Perform all necessary shutdown procedures on connected loads
before pressing this button twice.
Load/Battery Level Indicators (4 Green, 1 Amber)
The Load/Battery Level indicators have dual functions. During normal
mode operation LED indicators display the approximate electrical load
placed upon the UPS; and during battery mode operation LED indicators
display approximate battery capacity.
The UPStation GXT 2U is equipped with automatic and remote battery
test features. The automatic test occurs every 14 days (this option is user
configurable) if utility has not been interrupted. Should the battery fail this
test, the red fault indicator LED along with the A and C diagnostic LEDs
will illuminate and an alarm will sound (refer to Troubleshooting Guide).
The remote test feature functions with either MultiLink® 2 or MultiLink®
SNMP Manager software and can remotely initiate the battery test.
Fault Indicator LED (Red)
The Fault indicator LED is illuminated if the UPS has detected a problem.
Also, one or more of the load/battery level indicators may be illuminated
(Refer to Troubleshooting Guide).
Bypass Indicator LED (Amber)
The Bypass indicator LED is illuminated when the UPS is operating from
bypass power. An alarm will sound indicating the UPS detected a prob-
lem, or the manual bypass function has been activated.
UPS ON Indicator LED (Green)
The UPS ON indicator LED is illuminated when the UPS inverter is oper-
ating and supplying power to your connected loads.
Battery Indicator LED (Amber)
The Battery indicator LED is illuminated when the UPS is operating on
battery.