Figure 91 Equalize Time Period Screen; Figure 92 Equalize Voltage Screen; Figure 93 Battery Temperature Compensation Charge Screen - Liebert 30-130kVA Operation And Maintenance Manual

30-130kva, 60hz, single module system
Table of Contents

Advertisement

Figure 91 Equalize time period screen

When the battery is at full voltage (not being recharged), this selection reads EQUALIZE TIME
PERIOD (hrs). When the battery is recharging, this selection reads EQUALIZE TIME REMAINING
(hrs). After the equalize recharge time has expired, the indication returns to the preset equalize time.

Figure 92 Equalize voltage screen

The equalize voltage is also programmable. In the example above, the range is 520 to 580 volts with
the default being 540 volts.
Battery Temperature Compensation Charge
The Battery Temperature Compensation Charge screen is accessed from the Battery Management
Screen (Figure 83). The Operator can enable or disable Battery Temp Compensation function. He
can also change the compensation setting by going into the edit screen. The values are in millivolts/
degree C.

Figure 93 Battery temperature compensation charge screen

15 C =
20 C =
25 C =
30 C =
EQUALIZE TIME PERIOD
MIN
0
EQUALIZE VOLTAGE
MIN
520
540
BATTERY TEMP COMPENSATION CHARGE
<
TEMPERATURE
<
TEMPERATURE
<
TEMPERATURE
<
TEMPERATURE
NEXT
MAX
000
MAX
580
<
20 C
<
25 C
<
30 C
<
35 C
EXIT
61
72
850
1000
1000
850