Figure 103Auto Restart Setting Screen; Figure 104Auto Restart Screen Layout - Liebert 30-130kVA Operation And Maintenance Manual

30-130kva, 60hz, single module system
Table of Contents

Advertisement

Figure 103Auto restart setting screen

The source qualification timer dictates how long to allow for input and bypass voltages to return to
their nominal limits. The default value is 100 with a programmable range of 5-100 minutes. Since a
setting of 100 signifies an infinite wait time, the finite range can be set between 5 and 99 minutes.
Normally, 5 minutes is adequate.
Setting the Auto Restart to SYSTEM, automatically changes the setting for Motorized Battery
Breaker to "Motorized". The battery type setting cannot be changed back to Manual once Auto
Restart is set to YES. However, if Auto Restart Option is Disabled (Set to NO), battery type can be
independently set to Motorized. To access the proper screen, navigate to Configuration, then System
Settings, then Options, then Motorized Battery Breaker, and select Motorized.
Once in Auto Restart mode, a new screen will report the progress. (See Figure 104).

Figure 104Auto restart screen layout

The message, AUTO RESTART IN PROGRESS will be displayed during the Auto Restart sequence.
The text line below this message signifies the condition being checked, and flashes in reverse video
while the message is displayed.
The Operator can cancel the Auto Restart operation by selecting and acknowledging CANCEL. When
this is done, a message will appear asking, "Canceling will abort Auto Restart operation. Are you sure
you want to cancel? The Operator can then select YES or NO".
Alarm Notifications
At the start of Auto Restart operations, an alarm condition is recorded to log "Auto Restart Initiated".
If during the process Auto Restart is halted as a result of failed condition, a subsequent alarm is
recorded as "Auto Restart Failed". This will be a latched alarm and must be acknowledged and reset
by the Operator. See Alarm Messages on page 74 for a complete description of these alarms.
Auto Restart Trigger Condition
Any time the UPS detects and records an EOD (End of Discharge) condition occurring at the same
time the input contactor is open, it recognizes that the batteries can no longer support the load. This
scenario sets the Auto Restart flag, initiating the Auto Restart sequence.
In a Dual Input system, both Input and Bypass must be available to enable Auto Restart.
AUTO RESTART
AUTO RESTART SETTING
AUTO RESET TIMING
AUTO RESTART
AUTO RESTART IN PROGRESS
QUALIFYING INPUT POWER
CANCEL
SYSTEM
67
Operation
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Npower

Table of Contents