Table 7
Alarms, functions, and corrective actions (continued)
Actual
Alarm/fault
Name
Displayed
Description
On Front
of Alarm/
Panel
Fault
Delayed Batt
Delayed
Charge
Battery Charge
Reduced I
Reduced
Limit
Current Limit
Event Log
Event Log
Clear
Clear
Batt Not
Battery Not
Charging
Charging
UPSC-MM
UPSC-MM
comm. Fail
Comm Fail
User
User
Shutdown
Shutdown
Cannot
Cant Exec
Execute
Batt Test
Battery Test
Batt Not
Battery Not
Charged
Charged
System Time
Sys Time Set
Set By
By Op
Operator
Manual
Manual XFER
Transfer
Manual
Manual
ReXFER
Retransfer
Batt Cycle
Battery Cycle
Buff Full
Buffer Full
Fault
Or
Latch
Dial
Freeze
Alarm
Mask
Mask
Mask
Alarm
NO
NO
Alarm
NO
NO
Alarm
NO
NO
Alarm
YES
NO
Alarm
YES
YES
Alarm
YES
YES
Alarm
NO
NO
Alarm
NO
NO
Alarm
YES
YES
Alarm
NO
NO
Alarm
NO
NO
Alarm
NO
NO
Event Log
Mask
Meaning and Corrective Action(s)
The generator option is installed, the
system is on generator and the "Delayed
NO
YES
Battery Charge" is suppressing battery
charging to reduce the load on the
generator.
The UPS recognizes that the source is a
NO
YES
generator and has reduced the current limit
setting to avoid generator overloading.
Per the user request, all event logs have
been cleared. This will be the first alarm in
NO
YES
the new log. Momentary display. Sets flag
in the event history log.
With the battery breaker closed, the battery
voltage has not reached 95% of the units
"DC Float Voltage" set point within a
NO
YES
calculated time (based on the test duration.)
This calculation will start immediately at the
end of a successful ("Passed") battery self
test.
The UPS has detected a communication
failure between its UPS controls and it
NO
YES
monitoring system. Contact Liebert Global
Service.
The User has initiated an "Inverter Off" or
NO
YES
"System Shutdown" through the User
Shutdown screen.
The battery test could not be performed.
NO
YES
See 3.3.7 - Battery Management.
A battery test cannot be executed because
NO
YES
the battery charge is less than 90%.
The User has changed the Date or Time
NO
YES
from the front Panel. Momentary display.
Sets flag in the event history log.
The User has ordered a manual transfer
from UPS to Bypass from the front panel
NO
YES
controls. Momentary display. Sets flag in
the event history log.
The User has ordered a manual transfer
from Bypass to UPS from the front panel
NO
YES
controls. Momentary display. Sets flag in
the event history log.
With batt breaker closed, Monitor has
determined that the buffer that keeps track
NO
YES
of the number of hits the battery has taken
is full. No action required.
86