Liebert 30-130kVA Operation And Maintenance Manual page 89

30-130kva, 60hz, single module system
Table of Contents

Advertisement

Table 7
Alarms, functions, and corrective actions (continued)
Actual
Alarm/fault
Name
Displayed
Description
On Front
of Alarm/
Panel
Fault
Input
Input Over
OverVoltage
Voltage
Input current
Input Current
limit
Limit
Battery CB
Battery CB
Open
Open
Batt sup-
Batt Supp
plement is
Active
active
Bypass Sync
Bypass Sync
Error
Error
Bypass
Byp out
Voltage Out of
Tolerance
Tolerance
Bypass Line
Bypass Line
Fail
Fail
Fault
Or
Latch
Dial
Freeze
Alarm
Mask
Mask
Mask
Alarm
NO
NO
Alarm
NO
YES
Alarm
NO
YES
Alarm
NO
YES
Alarm
NO
YES
Alarm
NO
YES
Alarm
NO
YES
Event Log
Mask
Meaning and Corrective Action(s)
For all of these input problems the system
will supply power from the battery until the
end of discharge. At that point single input
NO
YES
systems will lose power to the load. Dual
input systems will attempt to transfer to
bypass if qualified and available. Call
Liebert Global Services for Assistance.
The RMS input current has reached the
NO
YES
Input Current Limit setting. Check the UPS
load.
The module battery circuit breaker (MBD) is
open. This circuit breaker might have been
opened either manually or automatically in
a UPS shutdown procedure. If the UPS is
operating with this breaker open, the critical
NO
YES
load is not protected from loss of the utility
source power. Manual closure of the battery
breaker is inhibited. You must use the front
panel to set up the sequence for manual
battery re-closure. Follow the instructions in
manual start-up.
This condition is indicated when the Batt
Discharging and Input Undervoltage alarms
are simultaneously active. The alarm will
NO
YES
clear when the Inp. Undervoltage alarm
clears and/or if the rectifier turns off and/or
if the Batt Dischg alarm clears.
The bypass is out of sync to a sufficient
degree that transfer to Static Bypass is
inhibited. An interrupted transfer will be
NO
YES
permitted only in the case of a critical fault.
If this alarm persists, contact Liebert Global
Services.
One or more bypass voltages is below 80%
or above 115% of the nominal value. If the
load is on UPS, and the unit is a dual input
unit, transfers to bypass will be inhibited. If
NO
YES
the unit is a single input unit, the system will
shut down. The Alarm will be cleared 5
seconds after all voltage are again with 85-
110% of nominal. If the load has been shut
down, re-start will be required.
The bypass source has dropped below 35V
per phase. On single input units, the UPS
will shut down. On dual input units, transfer
to the bypass will be inhibited. The alarm
NO
YES
will be cleared five seconds after all
voltages again exceed 45V. If the unit is
already on Bypass when this occurs, power
to the load will be lost.
81