There are two reasons why the
chimney in the house at right will cold
backdraft when it is cold outside and
there is no fire burning in the
fireplace. First, the chimney runs up
the outside of the house, so the air in
it is colder and denser than the warm
air in the house. And second, the
chimney is shorter than the heated
space of the house, meaning the
negative pressure low in the house
will pull outside air down the chimney,
through the fireplace and into the
room. Even the finest fireplace will not
work well when connected to this
chimney.

8.5 Chimney Installation Notes

1. If possible, install an interior chimney as it will provide better performance. In areas with
continuous temperatures below 18 C (0 F), the use of an exterior chimney increases
the likelihood of operating problems such as low draft, high rate of creosoting, and poor
start-up characteristics. Exterior chimneys are also prone to down-drafting and flow
reversal. Installations, which are located on lower floors in the house, such as in a
basement, in combination with outside chimney, are especially prone to flow reversal.
2. The MONACO is listed only with chimney systems described in TABLE 2 - LISTED
CHIMNEYS FOR YOUR MONACO.
3. A chimney venting a fireplace shall not vent any other appliance.
4. The minimum chimney system height for a straight installation is 15 ft. (4,6 m).
5. All chimney installations must include at least one support. Reducing the amount of
chimney weight on the fireplace will help avoid the noise created when the fireplace
expands. This can be achieved by having the chimney supported by the supports. The
maximum chimney length that should be supported by the fireplace is 9 ft. (2.75 m) for
2" Solid Pack Chimney and 12 ft. (3.7 m) for 1" Solid Pack Chimney.
6. The chimney must extend at least 3 ft. (92 cm) above its point of contact with the roof
and at least 2 ft. (61 cm) higher than any wall, roof or building within 10 ft. (3.1 m) of it.
See the figures on point 11 bellow to determine the configuration that applies to your
roof (flat or sloped roof and the distance between the chimney and the highest point of
the roof and/or the nearest chimney).