Monaco Installation and Operation Manual
7. When passing through a combustible wall or floor, a firestop must be installed at the wall or 
floor  penetration.  The  hole  size  must  be  in  accordance  with  the  duct  manufacturer's 
instructions. 
8. Do  not  connect  the  hot  air  ducts  to  a  central  heating  system.  Malfunction  of  the  heating 
system's fan will cause the fireplace to overheat.  
9. Do not use insulated flexible ducts as they may overheat. 
10. Do not use tees or any other components than the ones specifically listed here. 
11. All ducts must extend upwards or horizontally. Never route the ducting downwards. 
12. The  hot  air  outlet  grilles  must  be  installed  with  the  louvers  pointing  downwards  in  order  to 
prevent overheating adjacent ceilings. 
13. Always install the two outlet grilles when using the hot air outlet kit and blocking the upper 
louver of the fireplace. 