3. Secure the ducting (A) to the 90° elbows (E) with self‐tapping screws (3 per elbow). Insert the 
hot  air  outlets  (F)  in  the  elbow  (E).  Set  hot  air  outlets  frames  behind  the  non‐combustible 
materiel and secure to the wall with screws. Secure hot air outlets (F) to the elbows (E) with 3 
self‐tapping screws each. Secure the hot air outlets grilles to the frames with screws. 
4. Maintain at least a 2" (50 mm) clearance between the ducts and the firestop; the required hole 
size   for the hot air grilles (outlet) is 8¼" × 8¼" (210 mm × 210 mm). 
5. The maximum number of elbows in a run of duct is two. 
6. Maintain  at  least  10"  (254  mm)  clearance  from  the  outlet  grille  framing  to  a  combustible 
ceiling, side wall or mantel. 
 