Monaco Installation and Operation Manual
7. Deviations should be avoided whenever possible, especially the most pronounced.
Each deviation adds some restriction to the chimney system and may lead to draft
problems.
8. If the chimney extends higher than 5 ft. (1.5 m) above its point of contact with the roof,
it must be secured using a roof brace.
9. A rain cap must be installed on top of the chimney. Failure to install a rain cap may
cause corrosion problems.
10. Cut and frame square holes in all floors, ceilings, and roof that the chimney will go
through to provide a 2" (50 mm) minimum clearance between the chimney and any
combustible materials. Do not fill this 2 space with insulation or any other combustible
material.
11. Portions of the chimney which may extend through accessible spaces must be
enclosed to avoid contact with combustible materials or damage the chimney.