Initial Start-Up; Commissioning And Adjustment - Viessmann VITOSOL 200-T SD2A 2m2 Series Installation Instructions Manual

Table of Contents

Advertisement

Initial Start-up

Legend
Collector
Pressure relief valve
Solar-Divicon
Diaphragm expansion vessel
High-limit safety cut-out
Solar storage tank
Air vent c/w shut-off
Overflow container
T
Temperature sensors

Commissioning and Adjustment

For commissioning of the
solar heating system, refer
to the Vitosol Start-up,
Service and Operating
Instructions.
The collector circuit must be protected
in such a way that at the highest
possible collector temperature
(shutdown temperature) no heat
transfer fluid can escape from the
safety valve, or the air vent.
This is achieved by the appropriate
sizing of the expansion tank and
matching of the system pressure.
IMPORTANT
Under cold fill conditions, a minimum
static pressure must be maintained. It
can be calculated by the following:
15 psig +0.45 psig x_____h(ft.)
or
1.0 bar + 0.1 x_____h(m)
CAUTION
The pressure relief valve must be piped
to the overflow container or drain at all
times, since excessively hot fluid can
discharge from the system.
CAUTION
After de-aeration, the air vent c/w
shut-off at top of system must be
closed. To protect the solar system
from overheating in the summer, e.g.
during the holidays, do not shut down.
Appendix
49