L5" Dc Output Overcurrent (Instantaneous) - Daikin ESIE13-02 Service Manual

Table of Contents

Advertisement

Error Codes: Outdoor Units

"L5" DC Output Overcurrent (Instantaneous)

4.13
1
Remote controller
display
Method of
malfunction
detection
Malfunction
decision conditions
3
Supposed causes
4
5
Part 4 – Troubleshooting
L5
Malfunction is detected by converting the current flowing to power transistor into voltage with CT1 (DC
current sensor).
When overcurrent has run to power transistor.
(Actuated even by instantaneous overcurrent)
Faulty compressor coil (disconnection, poor insulation)
Compressor startup malfunction (mechanical lock)
Faulty inverter PC board
Instantaneous fluctuation of power supply voltage
Faulty compressor (if bearing is scratched)
The stop valve is left in closed.
128
ESIE13-02

Hide quick links:

Advertisement

Table of Contents
loading