Ukazuje na korisne savete ili dodatne informacije. Identification label Podatke o uređaju možete pronaći na identifikacionoj nalepnici, koja je smeštena na donjem delu desnog poklopca uređaja. D2CNL024A1AA Installation Manual Wall-mounted condensing boiler 3P469346-12P – 2020.07...
Odredišna zemlja (ili zemlje) About the unit Serijski broj Tip aparata This Daikin unit is a wall-mounted gas-fired condensing boiler that Klasa efikasnosti can supply heat to central heating systems, as well as supply Kategorija gasa Vrsta gasa i pritisak napajanja domestic hot water.
Automatic by-pass system: This ensures that the flow is at all times continued, to avoid overheating of the heat exchanger. This system is also supported with a special by-pass function in the control unit software. Dimensions Top view D2CNL024A1AA Installation Manual Wall-mounted condensing boiler 3P469346-12P – 2020.07...
Return temperature sensor Silencer Automatic air vent (pump) Water pressure sensor By-pass Boiler pump Domestic hot water flow sensor Domestic hot water flow limiter Filling valve Backflow preventer Flue gas adapter Installation Manual D2CNL024A1AA Wall-mounted condensing boiler 3P469346-12P – 2020.07...
3 About the unit Technical specifications Technical specifications Unit D2CNL024A1AA Heat Input Range(Qn) 4~23.5 Nominal Heat Output Range (Pn) at 80-60°C 3.8~22.8 Nominal Heat Output Range (Pn) at 50-30°C 4.4~24 Efficiency (30% partial load at 30°C return temperature) Central Heating Circuit Operating Pressure (min./max.)
3 Remove the front cover forwards (3). Control panel 5 Shift the control panel downwards (5) and then pull it forwards (6). Front cover 4 Loosen the two screws of the control panel (4). Installation Manual D2CNL024A1AA Wall-mounted condensing boiler 3P469346-12P – 2020.07...
Installation manual Wall-mounting bracket ▪ The boiler must be installed as instructed to limit the level of Installation template operating noise. Dowels and screws Condensate hose Cable glands 2×PG 7, 1×PG 9 Energy label D2CNL024A1AA Installation Manual Wall-mounted condensing boiler 3P469346-12P – 2020.07...
If antifreeze is needed for the system, the chosen antifreeze should not interact with rubber, commercial plastic and metal parts of the boiler that are in contact with the central heating water. Installation Manual D2CNL024A1AA Wall-mounted condensing boiler 3P469346-12P – 2020.07...
Daikin accepts no liability for any such damage or ineffectiveness caused by using inappropriate additive. Underfloor heating requirements Underfloor heating systems apparently require higher flow rate and Central heating return connection, 3/4"...
▪ During the electrical connections, make sure that the cables are like plastics. Metals like steel or copper are not allowed. well-fixed and are connected firmly and tightly. Installation Manual D2CNL024A1AA Wall-mounted condensing boiler 3P469346-12P – 2020.07...
Cable glands that are sent with the unit must be assembled to the bottom sheet of the boiler in case connection of these options. Below, you can see the cable glands placement. D2CNL024A1AA Installation Manual Wall-mounted condensing boiler 3P469346-12P – 2020.07...
4 Montaža 4.8.6 Wiring diagram OPASNOST: RIZIK OD ELEKTROKUCIJE Disconnect the power supply for more than 10 minutes before servicing Ext2 L Ext3* L NTC4 NTC3 NTC2 3WV1 PCB1 NTC1 NTC5 WPS1 Installation Manual D2CNL024A1AA Wall-mounted condensing boiler 3P469346-12P – 2020.07...
▪ Make sure that the condensate disposal system, the piping, and the fittings are made of acid resistant material like plastics. D2CNL024A1AA Installation Manual Wall-mounted condensing boiler 3P469346-12P – 2020.07...
L = 500-1000 mm The boiler manufacturer cannot be held responsible for Allowable flue length for C13x atmospheric conditions when siting flue terminals. Concentric 60/100 mm 11.0 m Concentric 80/125 mm 44.0 m Including 1 90° elbow Installation Manual D2CNL024A1AA Wall-mounted condensing boiler 3P469346-12P – 2020.07...
Page 17
60/100 mm. In this case, C13x and C33x flue systems should start with a 60/100 to 80/125 adapter coupled to the flue outlet. D2CNL024A1AA Installation Manual Wall-mounted condensing boiler 3P469346-12P – 2020.07...
Page 18
▪ Condensate flow into the unit is allowed. system must be obtained via Daikin. Type C53x (twin pipes flue system) Air supply and flue gas discharge from / to atmosphere in areas of different pressure.
500 mm DREXDUC0500AA length. 1000 mm DREXDUC1000AA Flue parts order codes Required flue kits and/or additional parts can be ordered from Daikin To fill the system with water with the order codes given in the table below: Flue part Order code OPREZ...
To fill the condensate trap Legend - User interface: INFORMACIJA Water must be poured into the inner tube. Fill the condensate trap by pouring 0.2 litres of water from the boiler flue outlet. Installation Manual D2CNL024A1AA Wall-mounted condensing boiler 3P469346-12P – 2020.07...
6 To quit sweeper mode, press "Reset" button. procedures. The CO values should be in limits as shown in below table. ▪ Explain the function and the use of the boiler heating and domestic hot water controls. D2CNL024A1AA Installation Manual Wall-mounted condensing boiler 3P469346-12P – 2020.07...
Page 22
▪ Emphasise that a comprehensive service should be carried out annually, especially before winter. ▪ Inform the householder of the guarantee and the requirement to register it to receive the full benefit of the warranty. Installation Manual D2CNL024A1AA Wall-mounted condensing boiler 3P469346-12P – 2020.07...
Page 24