Error Codes: Outdoor Units
1
Troubleshooting
3
4
5
Caution
Part 4 – Troubleshooting
Is
protection
HPS connector (*1)
correctly connected to
outdoor unit PC
board?
YES
Wait for 10 minutes after
the unit stops operating,
then check the following.
Is
there continuity in
each protection
HPS?
YES
Is there
continuity in lead
wire?
YES
*1 Connector symbol
ERLQ011~016*V3 / ERHQ011~016*V3: X32A (A1P)
ERLQ011~016*W1 / ERHQ011~016*W1: X32A (A2P)
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
NO
Connect correctly.
NO
NO
Replace the lead wire.
* Replace the outdoor unit PC board
(A1P) ERHQ***V3* / ERLQ***V3*
* Replace the inverter PC board (A2P )
ERHQ***W1* / ERLQ***W1*