Additional Checks for Troubleshooting

6
Additional Checks for Troubleshooting
1
6.1

Check No.1 - Outdoor Unit: Checking the Installation Condition

Check No.01
3
4
5
Part 4 – Troubleshooting
1 To check the installation condition, proceed as follows:
Check the spaces for all air
passage around the suction
and discharge areas.
Is the
minimum space respected?
Yes
Does the
discharged air from
other outdoor units cause an
increase of the suction
temperature?
Yes
Change the
installation location.
.
Change the
No
installation location.
Is the
No
heat exchanger
clean?
Yes
Is there enough
air flow?
Yes
Check the outdoor ambient
temperature R1T.
This temperature must be
lower than 43°C.
150
ESIE13-02
Clean the heat
No
exchanger.
Change the
installation location
No
or direction.