Error Codes: Outdoor Units
1
Troubleshooting
3
4
5
Part 4 – Troubleshooting
Is the supply
voltage within the range 180
to 220 VAC ?
YES
Turn OFF the power again (and
wait for 10 minutes).
-
-
Is
the fan
motor connector
correctly connected to
the outdoor PC board?
Is the connector X191A of
reactor coil (L4R) correctly
connected?
YES
Is there any
foreign matter around the
fan?
YES
Remove the fan motor connector.
Is the fan
rotatable easily
by hand?
YES
Check 10
check the fan motor.
A
(*) See also "Check No.10 - Outdoor Unit: Fan Speed Pulse" on page 159.
NO
NO
NO
NO
112
ESIE13-02
Ask repair so that the
supply voltage will be within
the normal range.
Properly connect the
connector.
Remove the foreign
matter.
Replace the fan motor.