E9" Malfunction Of Electronic Expansion Valve - Daikin ESIE13-02 Service Manual

Table of Contents

Advertisement

Error Codes: Outdoor Units

"E9" Malfunction of Electronic Expansion Valve

4.6
1
Remote controller
display
Method of
malfunction
detection
Malfunction
decision conditions
3
Supposed causes
4
5
Part 4 – Troubleshooting
E9
Method is determined according to the suction pipe superheat degree and electronic expansion valve
opening degree calculated by values of low pressure sensor and suction pipe temperature thermistor.
When the following conditions are met for 10 minutes
Suction pipe superheat degree < 4°C
Minimum electronic expansion valve opening degree
Connector of electronic expansion valve is missing when the power is on.
Faulty electronic expansion valve
Faulty solenoid valve
Faulty check valve
Disconnection of electronic expansion valve harness
Faulty connection of electronic expansion valve connector
Faulty each thermistor
Faulty mounting
Faulty pressure sensor
Faulty Outdoor control PC board