E7" Malfunction Of Outdoor Unit Fan Motor - Daikin ESIE13-02 Service Manual

Table of Contents

Advertisement

ESIE13-02

"E7" Malfunction of Outdoor Unit Fan Motor

4.5
E7
Remote controller
display
Method of
Abnormality of fan motor system is detected according to the fan speed detected by hall IC when the
malfunction
fan motor runs.
detection
Malfunction
decision conditions
Supposed causes
When the fan runs with speed less than a specified one for 15 seconds or more when the fan motor
running conditions are met
When connector detecting fan speed is disconnected
When malfunction is generated 4 times, the system shuts down.
Malfunction of fan motor
The harness connector between fan motor and PC board is left in disconnected, or faulty connector
Fan does not run due to foreign matters tangled
Malfunction of the outdoor (inverter) PC board
Blowout of fuse
111