"89" Water Heat Exchanger Frozen

3.2
89
User interface
display
Method of
The freeze-up protection control (operation halt) is activated during cooling operation according to the
malfunction
temperature detected by the hydro-box heat exchanger thermistor.
detection
Malfunction
Freeze-up protection:
decision conditions
When the hydro-box heat exchanger temperature is below 0°C during cooling operation.
Supposed causes
Troubleshooting
See also "Check No.4 - Resistance Conversion Table (Ambient, Coil, Fin)" on page 153.
Caution
Be sure to turn off power switch before connecting or disconnecting connector, otherwise parts may
be damaged.
Detection error due to faulty hydro-box heat exchanger thermistor.
Detection error due to faulty hydro-box PCB.
Check No. 04
Hydro-box heat exchanger
thermistor check
Is it
conform to the thermistor
characteristic
chart?
NO
YES
95
Error Codes: Hydro-box
Replace the hydro-box PCB.
Replace the thermistor (replace the
hydro-box PCB).
Part 4 – Troubleshooting