C. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specifi ed. Framing closer than the
minimums listed must be constructed entirely of noncom-
bustible materials (i.e., steel studs, concrete board, etc.)
Combustible Mantels
457
305
279
254
229
203
179
152
254
229
203
179
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
Figure 13.3 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
Non-Combustible Mantels
MAX.
406
254
229
203
179
152
102
76
127
51
13
25
102
MEASUREMENTS FROM TOP EDGE OF THE
FIRESCREEN DOOR ASSEMBLY
Figure 13.4 Minimum Vertical and Maximum Horizontal
Dimensions of Non-Combustibles
60
Note: All
measurements
in millimeters.
TO CEILING
787
635
330
305
279
Note: All
TO CEILING
measurements
in millimeters.
787
MIN.
305
152
127
Heat & Glo • RED40-N-AU, RED40ST-N-AU • 2294-900 Rev. G • 7/14
Combustible Mantel Legs Or Wall Projections
Extending Past The Face Of The Fireplace
5
FIREPLACE
OPENING
= ACCEPTABLE
NON-COMBUSTIBLE
MANTEL LEG
ZONE
Figure 13.5 Combustible Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
51 mm
102 mm
(2 in.)
(4 in.)
MIN.
MAX.
UNLIMITED
152 mm
(6 in.)
MIN.