Vmax Fuse Location; Thermistor Resistance Vs. Temperature - NTI VM110 Installation And Operation Instructions Manual

Vmax
Hide thumbs Also See for VM110:
Table of Contents

Advertisement

Vmax I&O Manual
Only replace Vmax VM110 & VM110P controller fuse with identical part (LFT 3.15A,
250V "slow-blow"). Failure to follow this warning may result in component failure or
property damage.
Figure 18-1 Vmax Fuse Location (Display Assembly Removed for Illustration Purposes)
Table 18-1 Thermistor Resistance vs. Temperature
Resistance Ohms (Ω)
Temp °F (°C)
-22 (-30)
-4 (-20)
14 (-10)
32 (0)
41 (5)
50 (10)
59 (15)
68 (20)
77 (25)
86 (30)
95 (35)
104 (40)
113 (45)
* Not applicable for Return Sensor, P/N 84745
Figure 14-1 Tft Model
Temp °F (°C)
176,133
122 (50)
96,761
131 (55)
55,218
140 (60)
32,650
149 (65)
25,390
158 (70)
19,900
167 (75)
15,710
176 (80)
12,490
185 (85)
10,000
194 (90)
8,057
203 (95)
6,531
212 (100)
5,327
230 (110)
4,369
-
Operating Fuse, LFT
3.15A – "Slow-blow"
Spare Fuse
Boiler Controller
Resistance Ohms (Ω)
3,603
2,986
2,488
2,083
1,752
1,481
1,258
1,072
918
789
680
506
-
│Troubleshooting
73