Overload bypass:
When enabled, the unit will
23
transfer to line mode if
overload occurs in battery
mode.
25
Record Fault code
Bulk charging voltage
26
(C.V voltage)
27
Floating charging voltage
Bypass disable
(default)
Record enable
1KVA default setting: 14.1V
2K/3KVA default setting: 28.2V
4K/5KVA default setting: 56.4V
If self-defined is selected in program 5, this program can
be set up. Setting range is from 12.0V to 14.6V for 1K
model, 24.0V to 29.2V for 2K/3K model and 48.0V to 58.4V
for 4K/5K model. Increment of each click is 0.1V.
1KVA default setting: 13.5V
2K/3KVA default setting: 27.0V
4K/5KVA default setting: 54.0V
If self-defined is selected in program 5, this program can
be set up. Setting range is from 12.0V to 14.6V for 1K
model, 24.0V to 29.2V for 2K/3K model and 48.0V to 58.4V
for 4K/5K model. Increment of each click is 0.1V.
21
Bypass enable
Record disable (default)