Programming - Siemens RVS41.813 User Manual

Avs75, avs37, qaa75, qaa78, qaa55 series heat pump controller
Table of Contents

Advertisement

Configuration
Settings
Used as
Direct adjustment
Operation lock
Siemens Switzerland Ltd
HVAC Products
5.2.2

Programming

A long press on the occupancy button (> 3 seconds) enables the service level to be
accessed. When the parameter is selected, the current value blinks. The setting knob is
used to adjust the value. The next setting can be selected by a short press on the
occupancy button.
Display
Function
ru = 1
The room unit is addressed as room unit 1 (default setting)
ru = 2
The room unit is addressed as room unit 2
ru = 3
The room unit is addressed as room unit 3
P1 = 1
Automatic storage:
A setpoint readjustment made with the knob is adopted either by pressing
the operating mode button or without any further confirmation (timeout).
P1 = 2
Storage with confirmation :
A setpoint readjustment made with the knob is adopted only after pressing
the operating mode button.
P2 = 0
OFF : All operating elements released (default setting)
P2 = 1
ON : Following operating elements are locked:
• Operating mode changeover heating circuit
• Readjustment of Comfort setpoint
• Changeover of operating level (occupancy button)
If operation lock is active and one of the locked buttons is pressed, OFF is displayed for
3 seconds.
The operation lock does not prevent the service level from being accessed.
User manual RVS61.843, RVS41.813
5 Handling
(default setting)
79/258