Frost protection

Heating curve

Heating curve slope
Heating curve
displacement
Adaption
86/258
Siemens Switzerland Ltd
HVAC Products
In Protection mode, the room temperature is prevented from falling below a certain
level. This means that the frost protection setpoint of the room temperature will be
maintained.
Line no.
HC1
HC2
HC3P
720
1020 1320
721
1021 1321
726
1026 1326
The heating curve generates the flow temperature setpoint, which is used to maintain a
certain flow temperature depending on the prevailing weather conditions. The heating
curve can be adjusted via a number of settings, thus matching heat output and room
temperature to individual needs.
The steeper the heating curve slope, the greater the change of flow temperature at low
outside temperatures. In other words, if the room temperature is not correct at low
outside temperatures, but at higher outside temperatures, the heating curve slope
needs readjusting.
Increasing the setting:
Decreasing the setting:
The set heating curve is based on a room temperature setpoint of 20 °C. If the room
temperature setpoint is adjusted, the heating curve adapts automatically to the new
value.
°C
100
90
80
70
60
50
40
30
20
10
Parallel displacement of the heating curve is used to change the flow temperature
evenly across the entire outside temperature range or, in other words, if the room
temperature is always too high or too low, a readjustment must be made via parallel
displacement.
Adaption of the heating curve is used by the controller to automatically adapt the
heating curve to the prevailing weather conditions. It can only be switched on or off. In
that case, a readjustment of heating curve slope and parallel displacement is not
required.
User manual RVS61.843, RVS41.813
6 The settings in detail
Operating line
Heating curve slope
Heating curve displacement
Heating curve adaption
Raises the flow temperature, especially when outside
temperatures are low.
Lowers the flow temperature, especially when outside
temperatures are low.
4
3
2,75
3,5
0
-10
-20
2,5
2,25
2
1,75
1,5
1,25
1
0,75
0,5
0,25
-30
°C
CE1U2355en_02