Switching differential
Charging time limitation
Charging time limitation

Overtemperature protection

162/258
Siemens Switzerland Ltd
HVAC Products
If the DHW temperature is lower than the current setpoint minus the switching
differential set here, DHW charging is started.
DHW charging is completed when the temperature reaches the current setpoint.
When DHW heating is released for the first time in a 24-hour period, forced charging is
initiated. DHW charging is also started when the DHW temperature lies within the
switching differential, provided it does not lie less than K below the setpoint.
Line no.
Operating line
5030
Charging time limitation
During DHW charging, space heating may obtain no or too little energy, depending on
the selected charging priority (1630) and the type of hydraulic circuit. For this reason, it
is often practical to set a time limit to DHW charging.
- - -
Charging time limitation is deactivated. The DHW is heated up to the nominal setpoint,
even if space heating cannot draw sufficient heat for a certain period of time.
10 – 600
DHW charging is stopped after the set period of time in minutes and then locked for the
same time before it is resumed. During this period of time, the heat produced is made
available for space heating. This cycle is repeated until the nominal DHW setpoint is
reached.
When space heating is switched off (summer operation, Eco function, etc.), DHW
charging will not be stopped, independent of the selected setting.
Line no.
Operating line
5050
Charging temp max
The solar collector charges the DHW storage tank until the set "Charging temp max" is
reached.
The "Protective collector overtemperature" function can reactivate the collector pump
until the maximum swimming pool temperature is reached.
The maximum charging temperature applies as well for the Legionella function. The
maximum charging temperature must be set the same as the set point for Legionella
function + switching differential when using the Legionella function.
User manual RVS61.843, RVS41.813
6 The settings in detail
CE1U2355en_02
28. September 2009