Release

Only RVS41..
Only RVS41..
106/258
Siemens Switzerland Ltd
HVAC Products
Line no.
Operating line
1620
Release
24h / day
Time programs HCs
Time program 4 / DHW
Low tariff
Time program 4 / DHW or LT
24h / day
The DHW temperature is maintained at the nominal DHW setpoint, independent of any
time programs.
Example:
0
6
Time programs HCs
The DHW setpoint changes between the nominal DHW setpoint and the reduced DHW
setpoint according to the heating circuits' time program. The first switch-on point of
each phase is shifted forward in time by one hour.
Example:
0
5
6
Time program 4 / DHW
For DHW heating, time program 4 of the local controller is taken into consideration. The
set switching times of that program are used to switch between the nominal DHW
setpoint and the reduced DHW setpoint. This way, the DHW storage tank is charged
independently of the heating circuits.
Example:
0
6
Low tariff
Released when the low-tariff input (E5) is active.
Time program 4 / DHW or LT
Released when DHW program 4 is set to nominal or the low-tariff input (E5) is active.
User manual RVS61.843, RVS41.813
6 The settings in detail
12
18
24
12
16 17
12
18
h
h
24
h
24
CE1U2355en_02
28. September 2009