6.14 Cascade; Control; Heat Source Sequence - Siemens RVS41.813 User Manual

Avs75, avs37, qaa75, qaa78, qaa55 series heat pump controller
Table of Contents

Advertisement

Control

Release integral source
seq
Reset integral heat
source seq
Switch-on delay

Heat source sequence

Auto source seq ch'over
148/258
Siemens Switzerland Ltd
HVAC Products
Defrost mode (air heat pumps)
Defrost mode is considered:
-
If the internal defrost function is active.
In defrost mode:
-
Energy acquisition is counted as employed energy heating
-
Energy supply is not counted
Reset fixed day storage
Line no.
Operating line
3190
Reset fixed day storage
The parameter Reset fixed day storage deletes the entire storage with all entries.
All entries or their values are displayed with "---".

6.14 Cascade

Line no.
Operating line
3530
Release integral source seq
3531
Reset integral source seq
3533
Switch-on delay
When, with the heat source currently in operation, the demand for heat cannot be met -
the difference being the release integral set here - another heat source is switched on.
When the value is increased, additional heat sources are switched on at a slower rate.
When the value is decreased, the heat sources are switched off at a faster rate.
When, with the heat source currently in operation, the demand for heat is exceeded by
the reset integral set here, the heat source with the highest priority is shut down.
When the value is increased, the heat sources operate for longer periods of time (in the
case of excess heat).
When the value is decreased, the heat sources are switched off at a faster rate.
Correct setting of the switch-on delay ensures that the plant maintains stable operating
states. This prevents frequent cycling of the heat sources.
With DHW requests, the delay time is fixed at one minute.
Line no.
Operating line
3540
Auto source seq ch'over
3541
Auto source seq exclusion
None
First
Last
First and last
@
With automatic source sequence changeover, the heat source loads in a cascade can
be influenced by defining the order of lead and lag heat source.
Fixed order
Setting - - - defines a fixed order.
The heat sources are switched on and off in the order of their LPB device addresses.
Order according to the number of operating hours
User manual RVS61.843, RVS41.813
6 The settings in detail
CE1U2355en_02
28. September 2009