Extension Module Avs75.390 - Siemens RVS41.813 User Manual

Avs75, avs37, qaa75, qaa78, qaa55 series heat pump controller
Table of Contents

Advertisement

Interfaces
Degree of protection and
safety class
Standards, safety, EMC,
etc.
Climatic conditions
Weight
Power supply
Wiring of terminals
Functional data
Inputs
Siemens Switzerland Ltd
HVAC Products
BSB
Max. cable length basic unit –
peripheral device
Max. total length
Min. cross-sectional area
LPB
With bus power supply via controller
(per controller)
With central bus power supply
Bus loading number
Degree of protection of housing to
EN 60 529
Safety class to EN 60 730
Degree of pollution to EN 60 730
CE conformity to
EMC directive
- Immunity
- Emissions
Low-voltage directive
– Electrical safety
Storage to EN 60721-3-1
Transport to EN 60721-3-2
Operation to EN 60721-3-3
Without packaging
8.2

Extension module AVS75.390

Rated voltage
Bemessungsfrequenz
Power consumption
Fusing of supply lines
(Power supply and outputs)
Software class
Mode of operation to EN 60 730
Digital inputs H2
Analog input H2
Mains input L
Sensor inputs BX6, BX7
User manual RVS61.843, RVS41.813
8 Technical data
2-wire connection, not interchangeable
200 m
400 m (max. cable capacitance) 60 nF)
2
0.5
mm
2
(copper cable 1.5 mm
, 2-wire not
interchangeable)
250 m
460 m
E = 3
IP 00
low-voltage-carrying parts meet the
requirements of safety class II, if correctly
installed
normal pollution
2004/108/EC
- EN 61000-6-2
- EN 61000-6-3
2006/95/EC
- EN 60730-1, EN 60730-2-9
class 1K3, temp. -20...65 °C
class 2K3, temp. -25...70°C
class 3K5, temp. -20...50°C (non-condensing)
RVS61.843: 607 g
RVS41.813 420 g
AC 230 V (+10% / -15%)
50/60 Hz
max. 4 VA
Automatic cutout: Max. 13 A to EN 60898-1
Fuse: Max. 10 AT
solid wire or stranded wire (twisted or with
ferrule):
1 core: 0.5...2.5 mm
2 cores 0.5...1.5 mm
A
1b (automatic operation)
safety extra low-voltage for potentialfree
low-voltage contacts:
voltage with contact open: DC 12 V
current with contact closed: DC 3 mA
protective extra low-voltage operating
range: DC (0...10) V
internal resistance: > 100 k Ω
AC 230 V ( ± 10 %)
internal resistance: > 100 k Ω
NTC 10k (QAZ36, QAD36)
2
2
243/258
CE1U2355en_02
28. September 2009