Parameterizing output 13 / 14 (output signal ON or RUN)

Application
One of these two states is output at output 13 / 14:
● ON
● RUN
You will find additional information in Chapters Operating principle (Page 11) and State
diagrams of the inputs and outputs (Page 71).
Use the output function ON, for instance, to implement latching if you selected pushbutton
control.
Use the Output function RUN in order, for instance, to control a line contactor connected
upstream.
Requirements
● Control supply voltage is connected.
● The 3RW50 soft starter does not signal any errors, the STATE / OVERLOAD LED is
extinguished.
Procedure
1. Start programming by pressing the MODE key longer than 2 seconds until the STATE /
OVERLOAD LED flickers green.
Press and hold the MODE key.
2. Also press the RESET / TEST key longer than 2 seconds until the LED STATE /
OVERLOAD illuminates red.
The set state of ON / RUN relay output is displayed on the SOFT TORQUE LED:
3. Release the MODE and RESET / TEST keys.
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
5.7 Parameterizing output 13 / 14 (output signal ON or RUN)
LED Soft Torque
Flashes green
Flickers green
Parameter assignment
Signal set on output 13 / 14
ON (factory setting)
RUN
99