Configuring The Magnetic Contacts; Testing The Magnetic Contacts - Response SA1 Installation & Operating Manual

Wirefree alarm systems
Table of Contents

Advertisement

When fixing the Detector with screws the top of
the Detector is secured with a keyhole slot over the
head of the smaller pan head screw. The bottom
of the Detector is secured using the 12mm
counter-sunk head screw fitted within the battery
compartment. Carefully drill out the centre of the
fixing screw hole in the battery compartment
using a 3mm drill. Do not over-tighten the fixing
screws as this may distort or damage the casing.
4. Fit the Magnet to the moving part of the door/window
opposite the Detector using the two 15mm fixing
screws. Ensuring that the parallel gap between the
Magnet and Detector is than 10mm and that the
arrow on the Magnet is pointing towards and aligned
with the mark on the top section on the Detector.
(Ensure back
surfaces are flush)
Magnet
Detector
5. If an additional wired Magnetic Contact is required,
this should be wired to the terminal block provided
in the battery compartment. The wired contact
should be connected using two core (24AWG) wire
of maximum length 1.5m.
A cable entry cut-out is provided beside the
terminal block in the battery cover.
6. Configure the Detector as described below.
7. Slide the batteries supplied into the battery holder,
ensuring that the positive (+) side is uppermost on
each battery as it is installed.
8. Carefully refit the battery holder onto the Detector
ensuring that the spring connectors slide onto
either side of the circuit board.
CONFIGURING THE MAGNETIC
CONTACTS
1. Located in the battery compartment is a row of 11
DIP switches.
2. DIP switches 1-8 are used to set the House Code
for the Magnetic Contact Detector and must be set
SA1/SA2/SAC1
to the same ON/OFF combination as the House
Code DIP switches in the Solar Siren.
Anti-Tamper
Hole for
Mounting
Screw
3. DIP Switches 9-11 must be set as follows for use
with this alarm system:
Alternative
4. If an additional wired contact is connected to the
Mounting
Detector, remove the jumper link S2 on the PCB.
IMPORTANT: If an additional wired contact is not
connected then jumper link SW2 must be fitted
for the detector to operate correctly.

TESTING THE MAGNETIC CONTACTS

Ensure that the system is in service mode.
1. Remove the battery cover from the Detector.
The LED on the Detector will illuminate for approx
1s as the battery cover is removed to indicate that
the tamper switch has been activated.
2. Open the door/window to remove the magnet from
the Detector. As the magnet is moved away from the
detector the LED will illuminate for approx 1s to
indicate that the Detector Contact has been triggered
3. If any external Magnetic Contact Sets are
connected to the Detector, operate these one at a
time. Each time a contact is opened the LED on
the Detector should illuminate for 1s to indicate
that it has been triggered.
4. Replace the battery cover on the Detector.
Terminal Block for Additional
Wired Magnetic Contact
Jumper
Switch
Link S2
House Code
DIP 9
DIP 10
ON
ON
Location of
Key-hole Screw
(underside)
Zone
DIP 11
OFF
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sa2Sac1

Table of Contents