System diagram

Parameter
7000
Select the system diagram during
commissioning.
This selection automatically enables
and monitors all components asso-
ciated with the respective scheme.
Access
"Device settings"
"Programming"
Language selection
Parameter
7001
Temperature differential heating
Parameter
7003
The heating limit temperature defines
the value of the outside temperature,
below which central heating com-
mences.
The heating limit temperature is the
result of the selected set room tem-
perature less the value entered under
"Temp. diff. heating".
Example:
System definition control settings
"System definition"
"System diagram"
l or m
Standard setting
Setting range
Note
For further information, see page 13.
Operating instructions
The selected set room temperature is
20 °C; the temperature entered under
"Temp. diff. heating" is 4,0 K.
Central heating commences if the
adjusted outside temperature drops
below 16 °C (heating limit tempera-
ture).
If the adjusted outside temperature
exceeds 18 °C, central heating stops
(because of the specified hysteresis
of 2 K).
2
0 to 11