DHW control settings
Cylinder temperature DHW
Parameter
6000
Switching times, DHW
Parameter
6001
Min. temperature
Parameter
6005
The minimum temperature prevents
the DHW temperature inside the DHW
cylinder from falling too low (frost pro-
tection).
Access
"Device settings"
"Programming"
"DHW"
Max. temperature
Parameter
6006
Renewed heating will be prevented after this max. temperature has been
reached inside the DHW cylinder, until the temperature has dropped by at least
5 K.
152
Operating instructions
Operating instructions
When the actual temperature falls
below the min. temperature, the DHW
cylinder is heat up to that value plus
hysteresis. This is independent of the
selected operating program.
If 2 cylinder temperature sensors are
fitted, only the top sensor will be used
to capture the temperature.
y to"Min. temp."
1 or !
Standard setting
Setting range
10 °C
5 to 60 °C

Hide quick links:

Advertisement