Buffer Cylinder Switching Times - Viessmann Vitocal 300-G Installation And Service Instructions Manual

Compact heat pump with electric drive type bw/bwc, ww/wwc
Table of Contents

Advertisement

Buffer cylinder
Parameter
7200
Note
This function is only available for system scheme 1 and 2.
When selecting system scheme 3 to
10, the buffer cylinder will be defined
automatically as a system compo-
nent.
Access
"Device settings"
"Programming"
y to "Buffer cylinder"

Buffer cylinder switching times

Parameter
7201
Fixed temperature
Parameter
7202
Note
This function is only available in
case of system scheme 1 and 2, if
the option "Yes" was selected under
"Buffer cylinder".
The temperature cannot be set
higher than that selected under
"Max. temp.".
Control settings, heating water buffer cylinder
In system scheme 2, if a heating
water buffer cylinder is part of the sys-
tem, that must be selected by opting
for "Yes".
"Buffer cylinder"
"YES" or "NO"
Standard setting
Setting range
Operating instructions
Setting of the temperature to which
the heating water buffer cylinder is
heated, if it is to be heated up and if
the "Fixed value" program was
selected under "Buffer cylinder
prog." (see operating instructions).
No
Yes/No
163