Page 1
VIESMANN Installation and service instructions for contractors Vitocal 300-G Type BW/BWS 301.B06 to B17 Type BWC 301.B06 to B17 Heat pump with electric drive, 1 and 2-stage ■ Brine/water heat pump: 5.7 to 34.4 kW With conversion kit to water/water heat pump: 7.5 to 45.2 kW ■...
Page 2
Safeguard the system against reconnection. ■ Wear suitable personal protective equipment when Please note ■ carrying out any work. Repairing components that fulfil a safety func- tion can compromise the safe operation of the system. Replace faulty components only with genuine Viessmann spare parts.
For replacements, use only original spare parts supplied or approved by Viessmann. Safety instructions for operating the system What to do if water escapes from the appliance Danger...
Page 4
Index Index 1. Information Disposal of packaging ................Symbols ....................Intended use ..................Product information ................Type BW 301.B and BWC 301.B ............■ Type BWS 301.B (heat pump stage 2) ..........■ System examples ................■ 2. Preparing for installation Designations in the system examples ...........
Page 5
Checking the sensors ................71 Viessmann NTC 10 k (blue marking) ..........73 Ω ■ Viessmann Pt500A (green marking) ........... 74 ■ Checking the fuses ................74 The appliance is too noisy ..............75 Condensation and moisture in the heat pump module ......75 6.
Please dispose of packaging waste in line with statu- DE: Use the disposal system organised by tory regulations. Viessmann. AT: Use the ARA statutory disposal system (Altstoff Recycling Austria AG, licence number 5766). CH: Packaging waste is disposed of by the HVAC contractor.
Type BW 301.B and BWC 301.B Design Central heating Vitocal 300-G, type BW 301.B and type BWC 301.B The heat pump can supply up to 3 heating circuits – are brine/water heat pumps for central heating, room 1 heating circuit without and 2 heating circuits with cooling and DHW heating in mono mode or mono mixer.
2 can be used both for central heating and for pump control unit of stage 1. DHW heating. A separate secondary pump and circu- lation pump for cylinder heating (both accessories) are therefore required for the heat pump stage 2. System examples Available system examples: See www.viessmann- schemes.com.
Page 9
Preparing for installation Designations in the system examples -2/145- --2/F14-- --2/F14-- --2/X3.8;3.9-- --2/211.2-- Fig. 1...
Page 10
Preparing for installation Primary circuit, type BW/BWC 301.B With water/water heat pump conversion kit: 1 primary pump Hydraulic installation scheme --2/X3.8;3.9-- --2/X3.8;3.9-- --------- Fig. 2 Note Type BWC 301.B is shown. In this case, the circulation pumps are fitted and connected at the factory (primary pump , secondary pump , circulation pump for...
Preparing for installation Primary circuit, type BW/BWC 301.B (cont.) Electrical installation scheme For an overview of the electrical connections and more information on the PCBs: See page 28 onwards and the separate service instructions for the "Vitotronic 200" heat pump control unit. With well pump connection 230 V~ 200 W sYYA...
Page 12
Preparing for installation Primary circuit, type BW 301.B + BWS 301.B (2-stage) With water/water heat pump conversion kit: 2 primary pumps Hydraulic installation scheme --F2-- --2/X3.8;3.9-- --2/224.2-- --2/211.1-- --F3-- --2/X3.8;3.9-- --------- Fig. 5 Equipment required Pos. Designation Pos. Designation Flow switch, well circuit (remove jumper before Heat pump stage 1 connecting) Heat pump control unit...
Page 13
Preparing for installation Primary circuit, type BW 301.B + BWS 301.B (2-stage) (cont.) Electrical installation scheme For an overview of the electrical connections and more information on the PCBs: See page 28 onwards and the "Vitotronic 200" service instructions. Well pump on-site connection 230 V~ 200 W 211.1 200 W...
Page 14
Preparing for installation Primary circuit, type BW 301.B + BWS 301.B (2-stage) (cont.) Connecting the sensors and limiters X3.3 230 V; 0.15 A X3.4 X3.8 230 V; 0.15 A X3.9 230 V; 0.15 A PT500 PT500 Fig. 8 With water/water heat pump conversion kit: 1 common primary pump Note If heat pump stages 1 and 2 (type BW 301.B and type BWS 301.B) are installed with different rated heating...
Page 15
Preparing for installation Primary circuit, type BW 301.B + BWS 301.B (2-stage) (cont.) Hydraulic installation scheme --F2-- --F3-- --2/X3.8;3.9-- --------- Fig. 9 Equipment required Pos. Designation Pos. Designation Dirt trap Heat pump stage 1 Well pump (suction pump for groundwater; con- Heat pump control unit nect via on-site contactor with fuse protection) 230 V connection: See page 13.
Page 16
Preparing for installation Primary circuit, type BW 301.B + BWS 301.B (2-stage) (cont.) Electrical installation scheme For an overview of the electrical connections and more information on the PCBs: See page 28 onwards and the separate "Vitotronic 200" service instructions. Well pump on-site connection 400 V~ 211.1 224.2...
Preparing for installation Requirements for on-site connections 1-stage (type BW 301.B, BWC 301.B) Heating water return and DHW cylinder return DHW cylinder flow (heating water side) Heating water flow < 42 V 230 V~ Primary circuit flow (heat pump brine in- let) Primary circuit return (heat pump brine outlet)
Page 18
Preparing for installation Requirements for on-site connections (cont.) 2-stage (type BW 301.B + BWS 301.B) < 42 V 230 V~ < 42 V 230 V~ 230 V~ 230 V~ < 42 V < 42 V Fig. 13 Type BWS on the left; type BW on the right Heating water return and DHW cylinder return DHW cylinder flow (heating water side) Heating water flow...
Page 19
Preparing for installation Siting and transport requirements Transport Please note Please note Impacts, compression and tensile loads can Tilting the compressor at a steep angle inside cause damage to the outside panels of the the heat pump can result in appliance damage. appliance.
Page 20
Preparing for installation Siting and transport requirements (cont.) Minimum clearances for 1-stage (type BW/ Minimum clearances for 2-stage (type BW 301.B + BWC 301.B) BWS 301.B) ≥ 400 ≥ 400 ≥ 100 Fig. 15 Fig. 14 Subject to on-site installation and site conditions ■...
Installation sequence Positioning the heat pump Fig. 16 1. Position the heat pump according to the details on 2. Align the appliance horizontally. page 19. Please note Operating the appliance without first remov- ing the transport brackets may cause vibra- tions and excessive noise.
Installation sequence Removing the top panel Fig. 17 Making the hydraulic connections For arrangement of hydraulic connections: See page 17. Connecting the primary circuit Please note The heat transfer medium can cause corrosion damage to on-site lines and components. The components and lines used must be resist- ant to the heat transfer medium.
4. Insulate pipes inside the building to prevent heat and safety valve (to DIN 4757). and vapour diffusion. Note 5. Charge the primary circuit with Viessmann heat ■ The expansion vessel must be approved to transfer medium and vent. DIN 4807. The diaphragms of the expansion ves-...
Installation sequence Electrical connection Preparing the electrical connections Cables Danger For cable lengths and cable cross-sections, see the Incorrect wiring can lead to serious injury from ■ following tables. electrical current and result in appliance dam- ■ For accessories: age. Cables with the required number of cores for exter- Take the following measures to prevent drifting nal connections.
Installation sequence Electrical connection (cont.) Installing the programming unit (type BW 301.B and BWC 301.B) Fig. 18 [XÖ Fig. 19...
Page 26
Installation sequence Electrical connection (cont.) Routing cables to the wiring chamber When routing the on-site power cables, observe the location of the cable entries into the appliance through its back panel: See page 17. < 42 V 230 V~/400 V~ Fig.
Page 27
Installation sequence Electrical connection (cont.) Making the electrical connection of heat pump stage 1 (type BW 301.B) and stage 2 (type BWS 301.B) < 42 V 230 V~ < 42 V 230 V~ Fig. 21 Wiring chamber, heat pump stage 2 (type 230 V~ connecting cables: BWS 301.B) ■...
Page 28
Installation sequence Electrical connection (cont.) Overview of the electrical connections of the heat pump control unit (type BW/BWC 301.B) 193C 193A 193B Fig. 22 Cross connect PCB: See page 36. Main PCB: See next chapter. F1 Fuse 6.3 A (slow) F3 Fuse 6.3 A (slow) Expansion PCB on main PCB: See page 32.
Page 29
Installation sequence Electrical connection (cont.) Plug Clamps Function Explanation 211.1 Primary pump (heat pump stage 1 Connection values ■ or common primary pump) Output: 200 W ■ Control of well pump Voltage: 230 V~ ■ ■ Max. switching current: 4(2) A ■...
Page 30
Installation sequence Electrical connection (cont.) Plug Clamps Function Explanation 212.1 Control of active cooling function AC-Box or on-site components for AC cooling Connection values Output: 10 W ■ Voltage: 230 V~ ■ Max. switching current: 4(2) A ■ 212.2 Heating circuit pump for heating cir- This pump is connected in addition to the secondary ■...
Page 31
Installation sequence Electrical connection (cont.) Connecting the temperature limiter, part no. 7151728, 7151729 to the mixer extension kit sÖ sÖ Fig. 25 Connect plug to the extension kit. sÖ Temperature limiter Heating circuit pump M3/HC3 Plug Terminals Function Explanation 214.1 External hook-up, heating/cooling cir- 230 V~ digital input: cuits:...
Page 32
Installation sequence Electrical connection (cont.) Plug Clamps Function Explanation 216.1 External hook-up, heating/cooling cir- 230 V~ digital input: cuits: 230 V~: Central heating demand for heating circuit ■ Central heating demand, heating cir- A1/HC1 active cuit A1/HC1 0 V: No demand ■...
Page 33
Installation sequence Electrical connection (cont.) Plug Clamps Function Explanation 222.2 Control of mixer motor for external Connection values heat generator Output: 10 W ■ Signal mixer OPEN Voltage: 230 V~ ■ Max. switching current: 0.2(0.1) A ■ 222.3 222.4 Control of external heat generators Floating contact and 1 high limit safety cut-out each (on site, max.
Page 34
Installation sequence Electrical connection (cont.) Plug Terminals Function Explanation 223.1 Central fault message Floating contact: 223.2 Closed: Fault ■ Open: No fault ■ Not suitable for safety LV ■ Connection values (contact rating): Voltage: 230 V~ ■ Max. switching current: 4(2) A ■...
Page 35
Installation sequence Electrical connection (cont.) Plug Terminals Function Explanation 224.7 Connection values Output: 100 W ■ Circulation pump for DHW reheating Voltage: 230 V~ ■ Max. switching current: 4(2) A ■ Control of immersion heater (in DHW cylinder) Immersion heater EHE 400 V~ 224.7 X2.N Fig.
Page 36
Installation sequence Electrical connection (cont.) Cross connect PCB (signal and safety connections) Set the required parameters during commissioning: See page 55 onwards. Terminals Function Explanation Fuse 6.3 A (slow) Note Observe the total load 1000 W of all connected compo- nents.
Page 37
Installation sequence Electrical connection (cont.) Terminals Function Explanation Note No parameters need to be set ■ No jumper should be installed if a power-OFF contact ■ is connected. The compressor is "forced" off as soon as the contact ■ opens. The power-OFF signal switches off the power supply ■...
Page 38
Installation sequence Electrical connection (cont.) Controller and sensor PCB (sensors) Set the required parameters during commissioning: See page 55 onwards. Plug Sensor/component Type F0.1/F0.2 Outside temperature sensor NTC 10 k Ω F0.2/F0.3 Radio clock receiver (on site) Buffer temperature sensor NTC 10 k Ω...
Page 39
— Viessmann appliances, e.g. ventilation unit Vitovent 300-F Note If further Viessmann appliances are to be connected to Modbus 1, plug in the Modbus distributor (accessories): See "Modbus distributor" installation in- structions. Connection, LON communication module (accessories): See "LON communi- —...
Page 40
Installation sequence Electrical connection (cont.) Connection of primary circuit flow/return temperature sensor, 2-stage heat pump < 42 V Fig. 29 Flow temperature sensor, primary circuit Return temperature sensor, primary circuit Using the cable ties provided, fasten sensor leads and dismantled leads (with plug ) together with the other low voltage leads.
Installation sequence Electrical connection (cont.) [{{] 0-10V L1 N Fig. 30 EA1 extension Circulation pump for swimming pool heating Power supply 1/N/PE 230 V/50 Hz (accessories) Junction box (on site) Temperature controller for swimming pool temper- ature control (floating contact: 230 V~, 0.1 A, Fuses and contactor for circulation pump for swim- ming pool heating (accessories) accessories)
Page 42
Installation sequence Power supply (cont.) Consult your power supply utility, which may offer dif- Protect the power cable for the heat pump control ■ ■ ferent supply tariffs for the main power circuits. unit with an MCB/fuse of max. 16 A. Observe the technical connection requirements of ■...
Page 43
Installation sequence Power supply (cont.) Type Recommended power cable Fuse protection Cable Max. cable length 301.B06 50 m C16A, 3-pole ■ 5 x 2.5 mm ■ 301.B08 50 m B16A, 3-pole 5 x 2.5 mm ■ 301.B10 50 m B16A, 3-pole 5 x 2.5 mm 301.B13 50 m...
Page 44
Installation sequence Power supply (cont.) 2-stage (type BW 301.B + BWS 301.B) X3.7 X3.6 ≈ Fig. 34 Shown without fuses and RCDs Heat pump control unit (connection on cross con- Backup fuse, ripple control receiver nect PCB) Feed: TNC system Instantaneous heating water heater (if installed) Economy tariff meter Compressor, heat pump stage 1 (type BW 301.B)
Page 45
Installation sequence Power supply (cont.) 1-stage (type BW/BWC 301.B) X3.7 X3.6 ≈ Fig. 35 Diagram excluding fuses and RCDs Heat pump control unit (connection on cross con- Premium tariff meter nect PCB) Ripple control receiver (contact open: Power-OFF Instantaneous heating water heater (if installed) enabled) with backup fuse Compressor Economy tariff meter...
Page 46
Installation sequence Power supply (cont.) 2-stage (type BW 301.B + BWS 301.B) X3.7 X3.6 ≈ Fig. 36 Shown without fuses and RCDs Heat pump control unit (connection on cross con- Premium tariff meter nect PCB) Ripple control receiver (contact open: Power-OFF Instantaneous heating water heater (if installed) enabled) with backup fuse Compressor, heat pump stage 1 (type BW 301.B)
Page 47
Installation sequence Power supply (cont.) Mains power supply in conjunction with on-site power consumption Without power-OFF E1E2 D /D L1 L1 L2 L2 L3 L3 Fig. 37 Heat pump Bi-directional meter (for PV systems to consume Additional consumers (of power generated on site) power on site): in the household Energy taken from power supply utility and energy...
Page 48
Installation sequence Power supply (cont.) Connection to EA1 extension Condition: "Enable Smart Grid 7E80" must be at "1". [{{] 0-10V Fig. 38 EA1 extension Floating N/O contact 2: The agreement of the Connection to controller and sensor PCB power supply utility may be required Floating N/O contact 1: The agreement of the Power supply 1/N/PE 230 V/50 Hz power supply utility may be required...
Page 49
Installation sequence Power supply (cont.) Phase monitor (if installed) The phase monitor monitors the compressor power LEDs explained in Fig. 40 ■ supply. "Rel" illuminates green: ■ ■ If the internal tolerance range is exceeded or under- All voltages and the rotating field (clockwise) are OK. shot, the phase monitor interrupts the safety chain ■...
Installation sequence Power supply (cont.) Version 3 LEDs explained in Fig. 42 Voltage "Un": ■ Illuminates green if voltage is present. Relay "R": ■ Illuminates yellow if the phase sequence is cor- rect. L1, L2, L3 Does not illuminate if the phase sequence is ■...
Page 51
Installation sequence Closing the heat pump (cont.) Fig. 43 Checking the diaphragm grommets Please note If the casing is not securely closed, this can lead to damage from condensation, vibrations and excessive noise. Seal the appliance so it is soundproof and dif- ■...
Commissioning, inspection, maintenance Opening the heat pump Danger Please note Contact with 'live' components can lead to seri- Commissioning immediately after installation ous injury from electric current. can lead to appliance damage. ■ Never touch the wiring chambers (for heat Wait at least 30 min between installing and pump control unit and power supply connec- commissioning the appliance.
Charge and vent the primary circuit before con- necting the power supply. 1. Check the pre-charge pressure of the expansion vessel. 2. Charge the primary circuit with Viessmann heat transfer medium and vent. Note Ensure frost protection down to 19 °C.
Commissioning, inspection, maintenance Checking expansion vessels and the primary circuit/heating circuit pres- sure Observe engineering information. Technical guides for heat pumps Checking the electrical connections for firm seating Commissioning the system Commissioning (configuration, parameter settings and Note function check) can be carried out with or without the The type and extent of the parameters depend on the commissioning wizard (see following chapter and serv- appliance type, on the selected system scheme and...
Page 56
Commissioning, inspection, maintenance Commissioning the system (cont.) Language Date/Time Time Date Start commissioning? Coding Parameter group Parameters level 1 select Temperature Sensor values sensors display Signal inputs Signal inputs display Actuator test Actuator test carry out Subscriber check (LON) Subscriber check carry out Function check Function...
Page 57
61. Energy meter, 3-phase: See page 64. — Ventilation unit: See page 62. — X Component is selected. For detailed information on system examples: See Component may be added. www.viessmann-schemes.com. Only in conjunction with a heating water buffer cylinder.
Page 58
Commissioning, inspection, maintenance Commissioning the system (cont.) Parameters for circulation pumps and other components Heating circuit pump Parameter Setting "System definition" Ó "System scheme 7000" With heating circuit A1/HC1 without ■ mixer With heating circuit M2/HC2 with ■ mixer With heating circuit M3/HC3 with ■...
Page 59
Commissioning, inspection, maintenance Commissioning the system (cont.) Vitocom 100, type GSM2 Parameter Setting "System definition" Ó "Vitocom 100 7017" "1" External extension Parameter Setting "System definition" Ó "External extension 7010" "1" EA1 extension "2" AM1 extension "3" EA1 and AM1 extensions Note For parameters for external functions, see the following table.
Page 60
Commissioning, inspection, maintenance Commissioning the system (cont.) External blocking of the compressor; mixer in control mode or CLOSED Parameter Setting "System definition" Ó "Effect of ext. blocking on heat pump/heating circuits 7015" "0" to "8" "Effect of external blocking on pumps/compressor 701A" "0"...
Page 61
Commissioning, inspection, maintenance Commissioning the system (cont.) Parameters for instantaneous heating water heater Parameter Setting "Electr booster heater" Ó "Enable instantaneous heating water heater 7900" "1" "Output for instant. heating water heater at power-OFF 790A" "1" 3 kW "2" 6 kW "3"...
Page 62
Commissioning, inspection, maintenance Commissioning the system (cont.) Possibly set additional parameters. Parameter Setting "System definition" Ó ≙ "Start hysteresis solar air absorber 7031" "0" to "500" ( 0 to 50 K) "Min. runtime to suppress summer mode 7035" "0" to "1440" min "Last calendar week for summer mode 7036"...
Page 63
Commissioning, inspection, maintenance Commissioning the system (cont.) Adjust values for Vitovent 200-W/300-C/300-W if necessary Parameter Setting "Ventilation" Ó "Set room temperature C108" Max. 4 K higher or lower than "Stand- ard room temperature 2000" (adjust- ≙ ment value: 1 0.1 °C) "Background ventilation C109"...
Page 64
Commissioning, inspection, maintenance Commissioning the system (cont.) Parameters for utilisation of power generated on site Parameter Setting "Photovoltaics" Ó "Enable own energy consumption PV 7E00" "1" ≙ "Threshold for electrical power 7E04" "0" to "300" ( 0 to 30 kW) Enable required functions for utilisation of power generated on site Parameter Setting...
Commissioning, inspection, maintenance Commissioning the system (cont.) Parameters for heat pump cascade Parameter Setting Lead heat pump Lag heat pump "Compressor" Ó "Enable use of compressor stage 5012" "0" to "15" — "System definition" Ó "System scheme 7000" "0" to "10" "11"...
Commissioning, inspection, maintenance Checking the system function Check the function of all system components: See 4. Start the required function, e.g. "DHW". Only those ■ "Function check". functions are shown that correspond to the actual ■ Call up temperatures at the heat pump control unit. system equipment level.
Maintenance Overview of internal components (cont.) Fig. 51 Flow temperature sensor, primary circuit (heat Low pressure sensor pump brine inlet) Suction gas temperature sensor Low pressure Schrader valve Safety high pressure switch High pressure Schrader valve High pressure sensor Instantaneous heating water heater (accessories) Filter dryer Primary pump (accessory for type BW 301.B) Return temperature sensor, primary circuit (heat...
Page 72
Maintenance Checking the sensors (cont.) Sensor Test element Outside temperature sensor (F0) NTC 10 k Ω ■ Buffer temperature sensor (F4) ■ Cylinder temperature sensor, top (F6) ■ Cylinder temperature sensor, bottom (F7) ■ Flow temperature sensor, heating circuit with mixer M2/HC2 (F12) ■...
Page 73
Maintenance Checking the sensors (cont.) Viessmann NTC 10 k (blue marking) Ω / °C R / k / °C R / k / °C R / k / °C R / k / °C R / k / °C R / k ϑ...
Maintenance Checking the sensors (cont.) Viessmann Pt500A (green marking) / °C / °C R / / °C R / / °C R / / °C R / / °C R / ϑ Ω ϑ Ω ϑ Ω ϑ Ω ϑ...
Page 75
Maintenance Checking the fuses (cont.) Danger Removing the fuse does not switch the power circuit to zero volt. Contact with 'live' compo- nents can lead to serious injury from electric cur- rent. Before working on the equipment, always ensure that the power circuit is also at zero volt.
Page 76
Maintenance Condensation and moisture in the heat pump… (cont.)
Page 77
Parts lists, type BWC 301.B Overview of the assemblies, type BWC 301.B The following details are required when ordering parts: ■ Serial no. (see type plate ■ Assembly (from this parts list) ■ Position number of the individual part within the assembly (from this parts list) Fig.
Page 78
Parts lists, type BWC 301.B Parts not shown, type BWC 301.B Pos. Part 0005 Touch-up paint stick, Vitosilver 0006 Touch-up spray paint, Vitosilver 0007 Installation and service instructions 0008 Operating instructions for Vitotronic 200, type WO1C 0009 Service instructions for Vitotronic 200, type WO1C...
Page 79
Parts lists, type BWC 301.B Parts not shown, type BWC 301.B (cont.)
Page 81
Parts lists, type BWC 301.B Casing, type BWC 301.B (cont.) Pos. Part 0001 Rubber buffer 0002 Hinge, upper part 0003 Hinge, lower part 0004 Adjustable foot with foot cap (4 pce) 0005 Side panel, left 0006 Side panel, right 0007 Top panel, back 0008 Back panel...
Page 83
Parts lists, type BWC 301.B Electrical equipment, type BWC 301.B (cont.) Pos. Part 0001 Programming unit, Vitotronic 200 heat pump control unit 0002 Controller and sensor PCB with cover (CU401) 0003 Base support, controller and sensor PCB (CU401) 0004 Main PCB with cover (MB761) 0005 Base support, main PCB (MB761) 0006...
Page 87
Parts lists, type BWC 301.B Hydraulics, type BWC 301.B (cont.) Pos. Part 0001 Gasket A 35 x 45 x 2 mm 0002 Spring clip, sensor 0003 Air vent valve G ⅜ 0004 Temperature sensor Pt500A 0005 Gasket A 30 x 44 x 2 mm 0006 Drain &...
Page 88
Parts lists, type BWC 301.B Hydraulics, type BWC 301.B (cont.)
Page 89
Parts lists, type BW 301.B Overview of the assemblies, type BW 301.B The following details are required when ordering parts: ■ Serial no. (see type plate ■ Assembly (from this parts list) ■ Position number of the individual part within the assembly (from this parts list) Fig.
Page 90
Parts lists, type BW 301.B Parts not shown, type BW 301.B Pos. Part 0005 Touch-up paint stick, Vitosilver 0006 Touch-up spray paint, Vitosilver 0007 Installation and service instructions 0008 Operating instructions for Vitotronic 200, type WO1C 0009 Service instructions for Vitotronic 200, type WO1C...
Page 91
Parts lists, type BW 301.B Parts not shown, type BW 301.B (cont.)
Page 93
Parts lists, type BW 301.B Casing, type BW 301.B (cont.) Pos. Part 0001 Rubber buffer 0002 Hinge, upper part 0003 Hinge, lower part 0004 Adjustable foot with foot cap (4 pce) 0005 Side panel, left 0006 Side panel, right 0007 Top panel, back 0008 Back panel...
Page 95
Parts lists, type BW 301.B Electrical equipment, type BW 301.B (cont.) Pos. Part 0001 Programming unit, Vitotronic 200 heat pump control unit 0002 Controller and sensor PCB with cover (CU401) 0003 Base support, controller and sensor PCB (CU401) 0004 Main PCB with cover (MB761) 0005 Base support, main PCB (MB761) 0006...
Page 99
Parts lists, type BW 301.B Hydraulics, type BW 301.B (cont.) Pos. Part 0001 Spring clip 0002 Air vent valve G ⅜ 0003 Gasket A 30 x 44 x 2 mm 0004 Drain & fill valve G ⅜ 0005 Spring clip D28 0006 Clip for threaded pipe D 31 35, M8, EPDM insert...
Page 100
Parts lists, type BW 301.B Hydraulics, type BW 301.B (cont.)
Page 101
Parts lists, type BWS 301.B Overview of the assemblies, type BWS 301.B The following details are required when ordering parts: ■ Serial no. (see type plate ■ Assembly (from this parts list) ■ Position number of the individual part within the assembly (from this parts list) Fig.
Page 102
Parts lists, type BWS 301.B Parts not shown, type BWS 301.B Pos. Part 0005 Touch-up paint stick, Vitosilver 0006 Touch-up spray paint, Vitosilver 0007 Vitocal installation and service instructions 0008 Operating instructions for Vitotronic 200, type WO1C 0009 Service instructions for Vitotronic 200, type WO1C...
Page 103
Parts lists, type BWS 301.B Parts not shown, type BWS 301.B (cont.)
Page 105
Parts lists, type BWS 301.B Casing, type BWS 301.B (cont.) Pos. Part 0001 Rubber buffer 0002 Hinge, upper part 0003 Hinge, lower part 0004 Adjustable foot with foot cap (4 pce) 0005 Side panel, left 0006 Side panel, right 0007 Top panel, back 0008 Back panel...
Page 106
Parts lists, type BWS 301.B Electrical equipment, type BWS 301.B 0030 0024 0025 0027 0009 0027 0025 0043 0050 0008 0057 0049 0055 Fig. 64...
Page 107
Parts lists, type BWS 301.B Electrical equipment, type BWS 301.B (cont.) Pos. Part 0008 PCB (IU210-A10 H_1 S_14) 0009 Full wave soft starter 0024 Compressor switching module 0025 Contactor, 3-pole 230 V~ 0027 Thermal relay 0030 Mains terminal, 5-pole 0043 Connecting cable, compressor 0049 Lead set, EEV sensors...
Page 111
Parts lists, type BWS 301.B Hydraulics, type BWS 301.B (cont.) Pos. Part 0001 Spring clip 0002 Air vent valve G ⅜ 0003 Gasket A 30 x 44 x 2 mm 0004 Drain & fill valve G ⅜ 0005 Spring clip D28 0006 Clip for threaded pipe D 31 35, M8, EPDM insert...
Commissioning/service reports Control parameters report (cont.) Parameter Code Delivered condition Commission- Maintenance/ service ≙ Set DHW temperature 6000 500 ( 50 °C) ≙ Min. DHW temperature 6005 100 ( 10 °C) ≙ Max. DHW temperature 6006 600 ( 60 °C) ≙...
Page 116
Commissioning/service reports Control parameters report (cont.) Electric booster heater Parameter Code Delivered condition Commission- Maintenance/ Service "Enable instantaneous heating water 7900 heater" "Enable electric heaters for DHW heat- 7901 ing" "Enable instant. heating water heater for 7902 central heating" Start delay instantaneous heating water 7905 30 min heater...
Page 117
Commissioning/service reports Control parameters report (cont.) Heating water buffer cylinder Parameters Code Delivered condition Commission- Maintenance/ service "Enable buffer cylinder/low loss header" 7200 ≙ "Temp in operating status fixed value for 7202 500 ( 50 °C) buffer cyl" ≙ "Hysteresis temperature heating buffer 7203 50 ( 5 K)
Page 119
Commissioning/service reports Control parameters report (cont.) Parameter Code Delivered condition Commission- Maintenance/ service Flow rate nominal ventilation 7D0B Vitovent 200-C: ■ 115 m Vitovent 300-F: ■ 170 m Flow rate intensive ventilation 7D0C Vitovent 200-C: ■ 155 m Vitovent 300-F: ■...
Page 120
Commissioning/service reports Control parameters report (cont.) Parameter Code Delivered condition Commission- Maintenance/ service Reduced ventilation C10A Vitovent 200-W: ■ 25 % Vitovent 300-C: ■ 75 m Vitovent 300-W: ■ 100 m Standard ventilation C10B Vitovent 200-W: ■ 50 % Vitovent 300-C: ■...
Page 121
Commissioning/service reports Control parameters report (cont.) Photovoltaics Parameter Code Factory setting Commission- Maintenance/ service "Enable own energy consumption PV" 7E00 ≙ "Prop. of external current" 7E02 10 ( 10 %) ≙ "Threshold for electrical power" 7E04 0 W) "Enable own energy consumptn for set 7E10 DHW temperature 2"...
Page 122
Commissioning/service reports Control parameters report (cont.) Communication Parameter Code Delivered condition Commission- Maintenance/ Service "Number of heat pump in cascade" 7707 "Enable LON communication module" 7710 "LON subscriber number" 7777 "LON fault manager" 7779 "LON system number" 7798 "Interval for data transfer via LON" 779C 20 min "Source outside temperature"...
Preferred appointment: Date Time Date Time The work that is requested to be carried out by Viessmann will be billed in accordance with the latest Viessmann pricelist. Place / Date Signature Final decommissioning and disposal Viessmann products can be recycled. Components...
Page 128
The product characteristics determined as system values for the product Vitocal 300-G (see technical guide) can be utilised to assess the energy consumption of heating and ventilation systems to DIN V 4701-10 specified by the EnEV [Germany].
Page 129
Keyword index Keyword index Cross connect PCB........28, 36, 67 Adjustable feet............21 Cylinder loading pump..........29 Air vent valve – Parameters..............58 – Primary side............70, 71 Cylinder temperature sensor........72 – Secondary side..........70, 71 – Bottom..............38 Ambient temperatures..........19 – Top................38 Appliance alignment...........21 Appliance fuse............74 Appliance too noisy............
Page 130
Keyword index Keyword index (cont.) Flow temperature sensor Maintenance work............53 – Cooling circuit............38, 72 Making the hydraulic connections......22 – Heating circuit............72 Maximum temperature limiter........30 – Heating circuit with mixer........39 MCB................42 – Heating circuit with mixer M2/HC2......38 Minimum clearances..........
Page 131
Keyword index Keyword index (cont.) Phase asymmetry............49 Room height...............19 Phase monitor..........49, 67, 68 Room temperature sensor – Version 1..............49 – Cooling circuit............38, 72 – Version 2..............49 – Heating circuit............72 – Version 3..............50 Photovoltaics..............64 Pipe entries..............23 Safety assembly............23 Positioning..............21 Safety chain...............
Page 132
Underfloor heating............30 Wiring chamber............ 26, 67 Underfloor heating circuit........23, 30 Undervoltage..............49 Use of power generated on site......... 42 Viessmann Werke GmbH & Co. KG Viessmann Limited D-35107 Allendorf Hortonwood 30, Telford Telephone: +49 6452 70-0 Shropshire, TF1 7YP, GB...