Choosing the Installation Site
Ensure that the location where you install your G350 fulfills the following requirements:
Cables are away from sources of electrical noise such as radio transmitters, broadcast amplifiers,
●
power lines, fluorescent light fixtures
Water or moisture cannot enter the case of the chassis.
●
Air can flow freely around all sides of the chassis.
●
The vents on the sides of the case are not blocked.
●
The installation is no more than 25 feet (7.6 m) from an approved ground.
●
Note:
If the G350 is more than 25 feet away from an approved ground, you must contact a licensed
Note:
electrician to install a supplementary ground conductor.
The environmental conditions match the following requirements:
●
Ambient temperature – 32
●
Relative humidity – 20-60% relative humidity
●
Minimum clearance for ventilation – 18 in. (45 cm)
●
Weight support – 20-22 lbs (9-10 kg)
●
8 Quick Start for Hardware Installation: Avaya G350 Media Gateway
o
o
o
o
to 104
F (0
to 40
C)