Choosing the Installation Site
Ensure that the location where you install your G250 fulfills the following requirements:
Cables are away from sources of electrical noise such as:
●
radio transmitters
●
broadcast amplifiers
●
power lines
●
fluorescent light fixtures
●
Water or moisture cannot enter the case of the chassis.
●
Air can flow freely around all sides of the chassis.
●
The vents on the sides of the case are not blocked.
●
The installation is no more than 16 feet (5 m) from an approved ground.
●
!
CAUTION:
If the installation location is more than 16 feet (5 m) feet away from an approved
CAUTION:
ground, do not install the Avaya G250 Media Gateway until a licensed electrician
is present to install a Supplementary Ground Conductor per Article 250 of the
National Electrical Code (NEC).
The environmental conditions match the requirements listed in
●
Table 2: Environmental Requirements
See Appendix A of Installing and Upgrading the Avaya G250 Media Gateway, 03-300434, for
additional information on environmental requirements.
Condition
Ambient temperature
Relative humidity
Minimum clearance for
ventilation
Weight support
Choosing the Installation Site
Table
Acceptable values
o
o
o
32
to 104
F (0
to 40
5% to 95%, non-condensing
2.5 in. (6.4 cm)
22 lb. (10 kg)
Issue 3 February 2007
2.
o
C)
9